Wire Size Calculator

Enter the load, distance and voltage. We check both NEC ampacity and voltage drop and recommend the smallest wire that passes both.

Free, no sign-upInstant resultsUpdated September 2026
A
%
3% branch, 5% total (NEC note)
Phase
Conductor
Recommended wire
–
How we calculated this

    For estimating and educational purposes only. Results are approximate and are not a substitute for a licensed professional, the manufacturer's instructions or your local code. Disclaimer

    How to size a wire

    A wire must pass two separate checks. First, its ampacity (how much current it can carry without overheating) must be at least the load current, or 125% of it for continuous loads. Second, the voltage drop over the run should stay under about 3% so motors, chargers and lights get enough voltage. On short runs ampacity decides the size; on long runs voltage drop usually does.

    Formula

    Required ampacity = Load amps × 1.25 (continuous loads) Voltage drop (1φ) = 2 × L × I × R ÷ 1000 Voltage drop (3φ) = 1.732 × L × I × R ÷ 1000 L = one-way length (ft), I = amps, R = Ω per 1000 ft

    Example: 40 A at 240 V, 150 ft, copper

    8 AWG copper is rated 50 A, so it passes ampacity. Its voltage drop is 2 × 150 × 40 × 0.764 ÷ 1000 = 9.2 V, or 3.8%, which is too high. 6 AWG gives 5.9 V (2.5%), so 6 AWG is the answer.

    Wire size chart (NEC 310.16, 75°C)

    SizeCopperAluminumTypical use
    14 AWG15 A*–Lighting circuits
    12 AWG20 A*15 A*Receptacles, kitchen
    10 AWG30 A*25 A*Water heater, dryer, A/C
    8 AWG50 A40 ARange, small subpanel
    6 AWG65 A50 AEV charger, subpanel
    4 AWG85 A65 ASubpanel feeder
    2 AWG115 A90 A90 A feeder
    1/0 AWG150 A120 AFeeders
    2/0 AWG175 A135 AFeeders
    4/0 AWG230 A180 A200 A service (Al, per 310.12)

    * Limited by NEC 240.4(D) small-conductor overcurrent rules.

    Frequently asked questions

    What size wire do I need for 50 amps?

    6 AWG copper (65 A at 75°C) is the usual choice for a 50 A circuit such as an EV charger or range. Long runs may need 4 AWG to keep voltage drop under 3%.

    What size wire for a 100 amp subpanel?

    Typically 3 AWG copper or 1 AWG aluminum at 75°C. Runs over about 100 ft often need one size larger for voltage drop.

    How far can I run 12 gauge wire on a 20 amp circuit?

    At 120 V and a full 16 A continuous load, 12 AWG copper stays under 3% drop up to about 58 ft one way. At lighter loads it can go farther.

    Is aluminum wire safe?

    Modern AA-8000 aluminum feeders are code-approved and common for services and feeders. Use connectors rated AL/CU and an anti-oxidant compound.