Transformer Size Calculator (kVA)

Get the standard kVA rating for your load and the full-load amps on each side.

Free, no sign-upInstant resultsUpdated October 2026
Phase
Load entered as
A
kW
More options
PF
%
Transformer size
–
How we calculated this

    For estimating and educational purposes only. Results are approximate and are not a substitute for a licensed professional, the manufacturer's instructions or your local code. Disclaimer

    Embed this calculator on your site

    Free for any website or blog. Copy the code below and paste it into an HTML block. Keep the credit link.

    Utility pole with a distribution transformer
    Utility pole with a distribution transformerPhoto: Jason Richard / Unsplash

    How to size a transformer

    Transformers are rated in kVA (apparent power). Calculate the load's kVA from its voltage and current, add a margin for future loads and continuous operation, and pick the next standard size.

    Single-phase kVA = V × I ÷ 1,000 Three-phase kVA = 1.732 × V × I ÷ 1,000 kVA from kW = kW ÷ Power factor Full-load amps = kVA × 1,000 ÷ (V or 1.732 × V)

    Example: 150 A at 208 V three-phase

    1.732 × 208 × 150 ÷ 1,000 = 54.0 kVA. With 25% margin: 67.5 kVA, so a 75 kVA transformer. Its full-load current is 90.2 A at 480 V primary and 208 A at 208 V secondary.

    Standard sizes

    TypeCommon kVA ratings
    Single-phase3, 5, 7.5, 10, 15, 25, 37.5, 50, 75, 100, 167
    Three-phase15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000

    Frequently asked questions

    How many amps is a 75 kVA transformer?

    At 208 V three-phase, 208 A. At 480 V three-phase, 90 A.

    Should a transformer be loaded to 100%?

    It can carry its nameplate load, but sizing for 75–80% leaves room for growth and reduces heat and losses.

    What is the difference between kVA and kW?

    kVA is apparent power; kW is real power. kW = kVA × power factor.