Transformers are rated in kVA (apparent power). Calculate the load's kVA from its voltage and current, add a margin for future loads and continuous operation, and pick the next standard size.
Single-phase kVA = V × I ÷ 1,000
Three-phase kVA = 1.732 × V × I ÷ 1,000
kVA from kW = kW ÷ Power factor
Full-load amps = kVA × 1,000 ÷ (V or 1.732 × V)
Example: 150 A at 208 V three-phase
1.732 × 208 × 150 ÷ 1,000 = 54.0 kVA. With 25% margin: 67.5 kVA, so a 75 kVA transformer. Its full-load current is 90.2 A at 480 V primary and 208 A at 208 V secondary.