Cable Size Calculator (mm²)

For metric installations: get the cable cross-section in mm² that carries your current and keeps voltage drop within limits.

Free, no sign-upInstant resultsUpdated October 2026
A
More options
%
Phase
Conductor
Cable size
–
How we calculated this

    For estimating and educational purposes only. Results are approximate and are not a substitute for a licensed professional, the manufacturer's instructions or your local code. Disclaimer

    Embed this calculator on your site

    Free for any website or blog. Copy the code below and paste it into an HTML block. Keep the credit link.

    Power cables stretching across a mountainous landscape
    Power cables stretching across a mountainous landscapePhoto: Daniele Turani / Unsplash

    How to calculate cable size

    The cable must carry the current without overheating (current-carrying capacity) and keep voltage drop low enough. We calculate the minimum area for each check and pick the next standard size that satisfies both.

    Min. area (1φ) = 2 × L × I × ρ ÷ ΔV Min. area (3φ) = 1.732 × L × I × ρ ÷ ΔV ρ copper ≈ 0.0225 Ω·mm²/m · ρ aluminum ≈ 0.036 Ω·mm²/m

    Example: 32 A, 30 m, 230 V single-phase, copper

    Allowed drop = 3% × 230 = 6.9 V. Area = 2 × 30 × 32 × 0.0225 ÷ 6.9 = 6.26 mm². Current capacity alone would allow 6 mm² (46 A), but voltage drop needs more, so the answer is 10 mm².

    Current capacity, copper PVC (IEC 60364-5-52, method C)

    Size2 loaded conductors3 loaded conductors
    1.5 mm²19.5 A17.5 A
    2.5 mm²27 A24 A
    4 mm²36 A32 A
    6 mm²46 A41 A
    10 mm²63 A57 A
    16 mm²85 A76 A
    25 mm²112 A96 A
    35 mm²138 A119 A
    50 mm²168 A144 A
    70 mm²213 A184 A

    Metric cable sizes 0.5–240 mm²: resistance, current capacity and AWG

    Solid-conductor diameter, DC resistance and current-carrying capacity of copper PVC cables to IEC 60364-5-52 for every standard cross-section.

    Show full table
    SizeØ solid (mm)Cu Ω/kmAl Ω/kmB1 2 cond.B1 3 cond.C 2 cond.C 3 cond.AWG (next size up)
    0.5 mm²0.8034.4856.53––––20 AWG
    0.75 mm²0.9822.9937.69––––18 AWG
    1 mm²1.1317.2428.26––––16 AWG
    1.5 mm²1.3811.4918.8417.5 A15.5 A19.5 A17.5 A14 AWG
    2.5 mm²1.786.89611.3124 A21 A27 A24 A12 AWG
    4 mm²2.264.3107.06632 A28 A36 A32 A10 AWG
    6 mm²2.762.8734.71141 A36 A46 A41 A8 AWG
    10 mm²3.571.7242.82657 A50 A63 A57 A6 AWG
    16 mm²4.511.0781.76676 A68 A85 A76 A4 AWG
    25 mm²5.640.68961.131101 A89 A112 A96 A3 AWG
    35 mm²6.680.49260.8075125 A110 A138 A119 A1 AWG
    50 mm²7.980.34480.5653151 A134 A168 A144 A1/0 AWG
    70 mm²9.440.24630.4038192 A171 A213 A184 A3/0 AWG
    95 mm²11.000.18150.2975232 A207 A258 A223 A4/0 AWG
    120 mm²12.360.14370.2355269 A239 A299 A259 A250 kcmil
    150 mm²13.820.11490.1884309 A275 A344 A299 A300 kcmil
    185 mm²15.350.093190.1528353 A314 A392 A341 A400 kcmil
    240 mm²17.480.071840.1178415 A370 A461 A403 A500 kcmil

    Resistance at 20 °C from ρ Cu = 0.017241 and ρ Al = 0.028264 Ω·mm²/m (nominal area; IEC 60228 allows slightly higher maximum values, e.g. 12.1 Ω/km for 1.5 mm²). Current capacity: copper, PVC insulation (70 °C), 30 °C ambient, IEC 60364-5-52 Table B.52.4 — method B1 = single cores in conduit on or in a wall, method C = cable clipped to a wall; 2 loaded conductors = single-phase, 3 = three-phase. 0.5–1 mm² are cords and control wiring (no fixed-installation rating). Apply grouping and ambient correction factors where needed.

    Frequently asked questions

    What size cable for 32 amps?

    6 mm² copper carries 32 A in most installations, but runs over about 20 m at 230 V usually need 10 mm² for voltage drop.

    How do I convert mm² to AWG?

    Approximate matches: 1.5 mm² ≈ 16 AWG, 2.5 mm² ≈ 14 AWG, 4 mm² ≈ 12 AWG, 6 mm² ≈ 10 AWG, 10 mm² ≈ 8 AWG, 16 mm² ≈ 6 AWG, 25 mm² ≈ 4 AWG.

    Why does the calculator suggest a bigger cable than the current table?

    On long runs voltage drop, not heating, decides the size.