How to calculate cable size
The cable must carry the current without overheating (current-carrying capacity) and keep voltage drop low enough. We calculate the minimum area for each check and pick the next standard size that satisfies both.
Example: 32 A, 30 m, 230 V single-phase, copper
Allowed drop = 3% × 230 = 6.9 V. Area = 2 × 30 × 32 × 0.0225 ÷ 6.9 = 6.26 mm². Current capacity alone would allow 6 mm² (46 A), but voltage drop needs more, so the answer is 10 mm².
Current capacity, copper PVC (IEC 60364-5-52, method C)
| Size | 2 loaded conductors | 3 loaded conductors |
|---|---|---|
| 1.5 mm² | 19.5 A | 17.5 A |
| 2.5 mm² | 27 A | 24 A |
| 4 mm² | 36 A | 32 A |
| 6 mm² | 46 A | 41 A |
| 10 mm² | 63 A | 57 A |
| 16 mm² | 85 A | 76 A |
| 25 mm² | 112 A | 96 A |
| 35 mm² | 138 A | 119 A |
| 50 mm² | 168 A | 144 A |
| 70 mm² | 213 A | 184 A |
Metric cable sizes 0.5–240 mm²: resistance, current capacity and AWG
Solid-conductor diameter, DC resistance and current-carrying capacity of copper PVC cables to IEC 60364-5-52 for every standard cross-section.
Show full table
| Size | Ø solid (mm) | Cu Ω/km | Al Ω/km | B1 2 cond. | B1 3 cond. | C 2 cond. | C 3 cond. | AWG (next size up) |
|---|---|---|---|---|---|---|---|---|
| 0.5 mm² | 0.80 | 34.48 | 56.53 | – | – | – | – | 20 AWG |
| 0.75 mm² | 0.98 | 22.99 | 37.69 | – | – | – | – | 18 AWG |
| 1 mm² | 1.13 | 17.24 | 28.26 | – | – | – | – | 16 AWG |
| 1.5 mm² | 1.38 | 11.49 | 18.84 | 17.5 A | 15.5 A | 19.5 A | 17.5 A | 14 AWG |
| 2.5 mm² | 1.78 | 6.896 | 11.31 | 24 A | 21 A | 27 A | 24 A | 12 AWG |
| 4 mm² | 2.26 | 4.310 | 7.066 | 32 A | 28 A | 36 A | 32 A | 10 AWG |
| 6 mm² | 2.76 | 2.873 | 4.711 | 41 A | 36 A | 46 A | 41 A | 8 AWG |
| 10 mm² | 3.57 | 1.724 | 2.826 | 57 A | 50 A | 63 A | 57 A | 6 AWG |
| 16 mm² | 4.51 | 1.078 | 1.766 | 76 A | 68 A | 85 A | 76 A | 4 AWG |
| 25 mm² | 5.64 | 0.6896 | 1.131 | 101 A | 89 A | 112 A | 96 A | 3 AWG |
| 35 mm² | 6.68 | 0.4926 | 0.8075 | 125 A | 110 A | 138 A | 119 A | 1 AWG |
| 50 mm² | 7.98 | 0.3448 | 0.5653 | 151 A | 134 A | 168 A | 144 A | 1/0 AWG |
| 70 mm² | 9.44 | 0.2463 | 0.4038 | 192 A | 171 A | 213 A | 184 A | 3/0 AWG |
| 95 mm² | 11.00 | 0.1815 | 0.2975 | 232 A | 207 A | 258 A | 223 A | 4/0 AWG |
| 120 mm² | 12.36 | 0.1437 | 0.2355 | 269 A | 239 A | 299 A | 259 A | 250 kcmil |
| 150 mm² | 13.82 | 0.1149 | 0.1884 | 309 A | 275 A | 344 A | 299 A | 300 kcmil |
| 185 mm² | 15.35 | 0.09319 | 0.1528 | 353 A | 314 A | 392 A | 341 A | 400 kcmil |
| 240 mm² | 17.48 | 0.07184 | 0.1178 | 415 A | 370 A | 461 A | 403 A | 500 kcmil |
Resistance at 20 °C from ρ Cu = 0.017241 and ρ Al = 0.028264 Ω·mm²/m (nominal area; IEC 60228 allows slightly higher maximum values, e.g. 12.1 Ω/km for 1.5 mm²). Current capacity: copper, PVC insulation (70 °C), 30 °C ambient, IEC 60364-5-52 Table B.52.4 — method B1 = single cores in conduit on or in a wall, method C = cable clipped to a wall; 2 loaded conductors = single-phase, 3 = three-phase. 0.5–1 mm² are cords and control wiring (no fixed-installation rating). Apply grouping and ambient correction factors where needed.
Frequently asked questions
What size cable for 32 amps?
6 mm² copper carries 32 A in most installations, but runs over about 20 m at 230 V usually need 10 mm² for voltage drop.
How do I convert mm² to AWG?
Approximate matches: 1.5 mm² ≈ 16 AWG, 2.5 mm² ≈ 14 AWG, 4 mm² ≈ 12 AWG, 6 mm² ≈ 10 AWG, 10 mm² ≈ 8 AWG, 16 mm² ≈ 6 AWG, 25 mm² ≈ 4 AWG.
Why does the calculator suggest a bigger cable than the current table?
On long runs voltage drop, not heating, decides the size.