Wire Size Calculator

Enter the load, distance and voltage. We check both NEC ampacity and voltage drop and recommend the smallest wire that passes both.

Free, no sign-upInstant resultsUpdated October 2026
A
More options
%
3% branch, 5% total (NEC note)
Phase
Conductor
Recommended wire
–
How we calculated this

    For estimating and educational purposes only. Results are approximate and are not a substitute for a licensed professional, the manufacturer's instructions or your local code. Disclaimer

    Embed this calculator on your site

    Free for any website or blog. Copy the code below and paste it into an HTML block. Keep the credit link.

    Electric cable at golden hour
    Electric cable at golden hourPhoto: Ernest Brillo / Unsplash

    How to size a wire

    A wire must pass two separate checks. First, its ampacity (how much current it can carry without overheating) must be at least the load current, or 125% of it for continuous loads. Second, the voltage drop over the run should stay under about 3% so motors, chargers and lights get enough voltage. On short runs ampacity decides the size; on long runs voltage drop usually does.

    Formula

    Required ampacity = Load amps × 1.25 (continuous loads) Voltage drop (1φ) = 2 × L × I × R ÷ 1000 Voltage drop (3φ) = 1.732 × L × I × R ÷ 1000 L = one-way length (ft), I = amps, R = Ω per 1000 ft

    Example: 40 A at 240 V, 150 ft, copper

    8 AWG copper is rated 50 A, so it passes ampacity. Its voltage drop is 2 × 150 × 40 × 0.764 ÷ 1000 = 9.2 V, or 3.8%, which is too high. 6 AWG gives 5.9 V (2.5%), so 6 AWG is the answer.

    Wire size chart (NEC 310.16, 75°C)

    SizeCopperAluminumTypical use
    14 AWG15 A*–Lighting circuits
    12 AWG20 A*15 A*Receptacles, kitchen
    10 AWG30 A*25 A*Water heater, dryer, A/C
    8 AWG50 A40 ARange, small subpanel
    6 AWG65 A50 AEV charger, subpanel
    4 AWG85 A65 ASubpanel feeder
    2 AWG115 A90 A90 A feeder
    1/0 AWG150 A120 AFeeders
    2/0 AWG175 A135 AFeeders
    4/0 AWG230 A180 A200 A service (Al, per 310.12)

    * Limited by NEC 240.4(D) small-conductor overcurrent rules.

    AWG wire gauge chart: 4/0 to 40 AWG

    Diameter, cross-section and copper resistance for every American Wire Gauge size from 0000 down to 40, computed from the exact AWG definition.

    Show full table
    AWGDiameter (in)Diameter (mm)Area (kcmil)Area (mm²)Cu Ω/1000 ftCu Ω/kmNearest metric
    4/0 (0000)0.460011.68211.6107.20.049010.1608120 mm²
    3/0 (000)0.409610.40167.885.030.061800.202895 mm²
    2/0 (00)0.36489.266133.167.430.077930.255770 mm²
    1/0 (0)0.32498.251105.553.480.098270.322450 mm²
    10.28937.34883.6942.410.12390.406650 mm²
    20.25766.54466.3733.630.15630.512735 mm²
    30.22945.82752.6326.670.19700.646425 mm²
    40.20435.18941.7421.150.24850.815225 mm²
    50.18194.62133.1016.770.31331.02816 mm²
    60.16204.11526.2513.300.39511.29616 mm²
    70.14433.66520.8210.550.49821.63410 mm²
    80.12853.26416.518.3660.62822.06110 mm²
    90.11442.90613.096.6340.79212.5996 mm²
    100.10192.58810.385.2610.99883.2776 mm²
    110.090742.3058.2344.1721.2604.1324 mm²
    120.080812.0536.5303.3091.5885.2114 mm²
    130.071961.8285.1782.6242.0036.5712.5 mm²
    140.064081.6284.1072.0812.5258.2852.5 mm²
    150.057071.4503.2571.6503.18410.451.5 mm²
    160.050821.2912.5831.3094.01513.171.5 mm²
    170.045261.1502.0481.0385.06316.611 mm²
    180.040301.0241.6240.82306.38520.950.75 mm²
    190.035890.91161.2880.65278.05126.410.75 mm²
    200.031960.81181.0220.517610.1533.310.5 mm²
    210.028460.72290.81010.410512.8042.000.5 mm²
    220.025350.64380.64240.325516.1452.96–
    230.022570.57330.50950.258220.3666.78–
    240.020100.51060.40400.204725.6784.21–
    250.017900.45470.32040.162432.37106.2–
    260.015940.40490.25410.128840.81133.9–
    270.014200.36060.20150.102151.47168.9–
    280.012640.32110.15980.0809864.90212.9–
    290.011260.28590.12670.0642281.83268.5–
    300.010030.25460.10050.05093103.2338.5–
    310.0089280.22680.079700.04039130.1426.9–
    320.0079500.20190.063210.03203164.1538.3–
    330.0070800.17980.050130.02540206.9678.8–
    340.0063050.16010.039750.02014260.9856.0–
    350.0056150.14260.031520.01597329.01,079–
    360.0050000.12700.025000.01267414.81,361–
    370.0044530.11310.019830.01005523.11,716–
    380.0039650.10070.015720.007967659.62,164–
    390.0035310.089690.012470.006318831.82,729–
    400.0031450.079870.0098880.0050101,0493,441–

    Solid annealed copper at 20 °C (ρ = 1.7241 × 10⁻⁸ Ω·m, 100 % IACS). d = 0.005 in × 92(36 − n)/39; 0000 = n −3. Stranded wire is about 2–3 % larger in diameter and slightly higher in resistance (NEC Chapter 9, Table 8). Nearest metric = closest IEC size by area (within ±30 %), not an equivalent ampacity.

    Copper wire ampacity: NEC Table 310.16 (60 / 75 / 90 °C)

    Allowable ampacity of insulated copper conductors, not more than three current-carrying conductors in a raceway, cable or earth, 30 °C (86 °F) ambient.

    Show full table
    AWG60 °C (TW, UF, NM-B)75 °C (THWN, XHHW)90 °C (THHN, XHHW-2)Max. breaker (240.4(D))Area (mm²)
    1415 A*20 A*25 A*15 A2.08
    1220 A*25 A*30 A*20 A3.31
    1030 A*35 A*40 A*30 A5.26
    840 A50 A55 A–8.37
    655 A65 A75 A–13.3
    470 A85 A95 A–21.2
    385 A100 A115 A–26.7
    295 A115 A130 A–33.6
    1110 A130 A145 A–42.4
    1/0125 A150 A170 A–53.5
    2/0145 A175 A195 A–67.4
    3/0165 A200 A225 A–85.0
    4/0195 A230 A260 A–107.0

    Table values from NEC 2023 Table 310.16. * 14, 12 and 10 AWG copper are limited to 15, 20 and 30 A overcurrent protection by NEC 240.4(D) regardless of insulation. Use the 90 °C column only for derating; the final ampacity may not exceed the terminal rating (usually 60 °C up to 100 A, 75 °C above, NEC 110.14(C)). NM-B cable is always sized at 60 °C.

    Frequently asked questions

    What size wire do I need for 50 amps?

    6 AWG copper (65 A at 75°C) is the usual choice for a 50 A circuit such as an EV charger or range. Long runs may need 4 AWG to keep voltage drop under 3%.

    What size wire for a 100 amp subpanel?

    Typically 3 AWG copper or 1 AWG aluminum at 75°C. Runs over about 100 ft often need one size larger for voltage drop.

    How far can I run 12 gauge wire on a 20 amp circuit?

    At 120 V and a full 16 A continuous load, 12 AWG copper stays under 3% drop up to about 58 ft one way. At lighter loads it can go farther.

    Is aluminum wire safe?

    Modern AA-8000 aluminum feeders are code-approved and common for services and feeders. Use connectors rated AL/CU and an anti-oxidant compound.