What is voltage drop?
Every wire has resistance, so some voltage is lost as current flows through it. The longer the run and the higher the current, the bigger the loss. Too much drop makes motors run hot, LEDs flicker and chargers slow down.
Voltage drop formula
L is the one-way length in feet, I is the current in amps, and R is the conductor resistance in ohms per 1,000 ft from NEC Chapter 9, Table 8.
Example
10 AWG copper, 24 A, 100 ft, 240 V single-phase: 2 × 100 × 24 × 1.21 ÷ 1000 = 5.81 V, which is 2.42%. That is within the 3% recommendation.
Recommended limits
The NEC informational notes in 210.19 and 215.2 recommend no more than 3% on a branch circuit or feeder and 5% total from the service to the farthest outlet. These are recommendations, but many inspectors and equipment manufacturers expect them.
Resistance per 1,000 ft (NEC Ch. 9, Table 8)
| Size | Copper Ω | Aluminum Ω |
|---|---|---|
| 14 AWG | 3.07 | – |
| 12 AWG | 1.93 | 3.18 |
| 10 AWG | 1.21 | 2.00 |
| 8 AWG | 0.764 | 1.26 |
| 6 AWG | 0.491 | 0.808 |
| 4 AWG | 0.308 | 0.508 |
| 2 AWG | 0.194 | 0.319 |
| 1/0 AWG | 0.122 | 0.201 |
| 2/0 AWG | 0.0967 | 0.159 |
| 4/0 AWG | 0.0608 | 0.100 |
Maximum wire length for 3% voltage drop at 120 V
Longest one-way run (in feet) for each copper wire size and load current before the voltage drop reaches 3% on a 120 V single-phase circuit.
Show full table
| AWG | 10 A | 15 A | 20 A | 30 A | 40 A | 50 A | 60 A | 80 A | 100 A | 150 A | 200 A |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 14 | 59 ft | 39 ft | – | – | – | – | – | – | – | – | – |
| 12 | 93 ft | 62 ft | 47 ft | – | – | – | – | – | – | – | – |
| 10 | 149 ft | 99 ft | 74 ft | 50 ft | – | – | – | – | – | – | – |
| 8 | 236 ft | 157 ft | 118 ft | 79 ft | 59 ft | 47 ft | – | – | – | – | – |
| 6 | 367 ft | 244 ft | 183 ft | 122 ft | 92 ft | 73 ft | 61 ft | – | – | – | – |
| 4 | 584 ft | 390 ft | 292 ft | 195 ft | 146 ft | 117 ft | 97 ft | 73 ft | – | – | – |
| 3 | 735 ft | 490 ft | 367 ft | 245 ft | 184 ft | 147 ft | 122 ft | 92 ft | 73 ft | – | – |
| 2 | 928 ft | 619 ft | 464 ft | 309 ft | 232 ft | 186 ft | 155 ft | 116 ft | 93 ft | – | – |
| 1 | 1,169 ft | 779 ft | 584 ft | 390 ft | 292 ft | 234 ft | 195 ft | 146 ft | 117 ft | – | – |
| 1/0 | 1,475 ft | 984 ft | 738 ft | 492 ft | 369 ft | 295 ft | 246 ft | 184 ft | 148 ft | 98 ft | – |
| 2/0 | 1,861 ft | 1,241 ft | 931 ft | 620 ft | 465 ft | 372 ft | 310 ft | 233 ft | 186 ft | 124 ft | – |
| 3/0 | 2,350 ft | 1,567 ft | 1,175 ft | 783 ft | 587 ft | 470 ft | 392 ft | 294 ft | 235 ft | 157 ft | 117 ft |
| 4/0 | 2,961 ft | 1,974 ft | 1,480 ft | 987 ft | 740 ft | 592 ft | 493 ft | 370 ft | 296 ft | 197 ft | 148 ft |
Copper, NEC Chapter 9 Table 8 resistance (75 °C), power factor 1: L = 0.03 × V × 1000 ÷ (2 × I × RΩ/kft). “–” = current above the wire's 75 °C ampacity (or the 240.4(D) limit). For a 5% limit multiply by 5/3; for aluminum divide by about 1.65.
Maximum wire length for 3% voltage drop at 240 V
Longest one-way run (in feet) for each copper wire size and load current before the voltage drop reaches 3% on a 240 V single-phase circuit.
Show full table
| AWG | 10 A | 15 A | 20 A | 30 A | 40 A | 50 A | 60 A | 80 A | 100 A | 150 A | 200 A |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 14 | 117 ft | 78 ft | – | – | – | – | – | – | – | – | – |
| 12 | 187 ft | 124 ft | 93 ft | – | – | – | – | – | – | – | – |
| 10 | 298 ft | 198 ft | 149 ft | 99 ft | – | – | – | – | – | – | – |
| 8 | 471 ft | 314 ft | 236 ft | 157 ft | 118 ft | 94 ft | – | – | – | – | – |
| 6 | 733 ft | 489 ft | 367 ft | 244 ft | 183 ft | 147 ft | 122 ft | – | – | – | – |
| 4 | 1,169 ft | 779 ft | 584 ft | 390 ft | 292 ft | 234 ft | 195 ft | 146 ft | – | – | – |
| 3 | 1,469 ft | 980 ft | 735 ft | 490 ft | 367 ft | 294 ft | 245 ft | 184 ft | 147 ft | – | – |
| 2 | 1,856 ft | 1,237 ft | 928 ft | 619 ft | 464 ft | 371 ft | 309 ft | 232 ft | 186 ft | – | – |
| 1 | 2,338 ft | 1,558 ft | 1,169 ft | 779 ft | 584 ft | 468 ft | 390 ft | 292 ft | 234 ft | – | – |
| 1/0 | 2,951 ft | 1,967 ft | 1,475 ft | 984 ft | 738 ft | 590 ft | 492 ft | 369 ft | 295 ft | 197 ft | – |
| 2/0 | 3,723 ft | 2,482 ft | 1,861 ft | 1,241 ft | 931 ft | 745 ft | 620 ft | 465 ft | 372 ft | 248 ft | – |
| 3/0 | 4,700 ft | 3,133 ft | 2,350 ft | 1,567 ft | 1,175 ft | 940 ft | 783 ft | 587 ft | 470 ft | 313 ft | 235 ft |
| 4/0 | 5,921 ft | 3,947 ft | 2,961 ft | 1,974 ft | 1,480 ft | 1,184 ft | 987 ft | 740 ft | 592 ft | 395 ft | 296 ft |
Copper, NEC Chapter 9 Table 8 resistance (75 °C), power factor 1: L = 0.03 × V × 1000 ÷ (2 × I × RΩ/kft). “–” = current above the wire's 75 °C ampacity (or the 240.4(D) limit). For a 5% limit multiply by 5/3; for aluminum divide by about 1.65.
AWG wire gauge chart: 4/0 to 40 AWG
Diameter, cross-section and copper resistance for every American Wire Gauge size from 0000 down to 40, computed from the exact AWG definition.
Show full table
| AWG | Diameter (in) | Diameter (mm) | Area (kcmil) | Area (mm²) | Cu Ω/1000 ft | Cu Ω/km | Nearest metric |
|---|---|---|---|---|---|---|---|
| 4/0 (0000) | 0.4600 | 11.68 | 211.6 | 107.2 | 0.04901 | 0.1608 | 120 mm² |
| 3/0 (000) | 0.4096 | 10.40 | 167.8 | 85.03 | 0.06180 | 0.2028 | 95 mm² |
| 2/0 (00) | 0.3648 | 9.266 | 133.1 | 67.43 | 0.07793 | 0.2557 | 70 mm² |
| 1/0 (0) | 0.3249 | 8.251 | 105.5 | 53.48 | 0.09827 | 0.3224 | 50 mm² |
| 1 | 0.2893 | 7.348 | 83.69 | 42.41 | 0.1239 | 0.4066 | 50 mm² |
| 2 | 0.2576 | 6.544 | 66.37 | 33.63 | 0.1563 | 0.5127 | 35 mm² |
| 3 | 0.2294 | 5.827 | 52.63 | 26.67 | 0.1970 | 0.6464 | 25 mm² |
| 4 | 0.2043 | 5.189 | 41.74 | 21.15 | 0.2485 | 0.8152 | 25 mm² |
| 5 | 0.1819 | 4.621 | 33.10 | 16.77 | 0.3133 | 1.028 | 16 mm² |
| 6 | 0.1620 | 4.115 | 26.25 | 13.30 | 0.3951 | 1.296 | 16 mm² |
| 7 | 0.1443 | 3.665 | 20.82 | 10.55 | 0.4982 | 1.634 | 10 mm² |
| 8 | 0.1285 | 3.264 | 16.51 | 8.366 | 0.6282 | 2.061 | 10 mm² |
| 9 | 0.1144 | 2.906 | 13.09 | 6.634 | 0.7921 | 2.599 | 6 mm² |
| 10 | 0.1019 | 2.588 | 10.38 | 5.261 | 0.9988 | 3.277 | 6 mm² |
| 11 | 0.09074 | 2.305 | 8.234 | 4.172 | 1.260 | 4.132 | 4 mm² |
| 12 | 0.08081 | 2.053 | 6.530 | 3.309 | 1.588 | 5.211 | 4 mm² |
| 13 | 0.07196 | 1.828 | 5.178 | 2.624 | 2.003 | 6.571 | 2.5 mm² |
| 14 | 0.06408 | 1.628 | 4.107 | 2.081 | 2.525 | 8.285 | 2.5 mm² |
| 15 | 0.05707 | 1.450 | 3.257 | 1.650 | 3.184 | 10.45 | 1.5 mm² |
| 16 | 0.05082 | 1.291 | 2.583 | 1.309 | 4.015 | 13.17 | 1.5 mm² |
| 17 | 0.04526 | 1.150 | 2.048 | 1.038 | 5.063 | 16.61 | 1 mm² |
| 18 | 0.04030 | 1.024 | 1.624 | 0.8230 | 6.385 | 20.95 | 0.75 mm² |
| 19 | 0.03589 | 0.9116 | 1.288 | 0.6527 | 8.051 | 26.41 | 0.75 mm² |
| 20 | 0.03196 | 0.8118 | 1.022 | 0.5176 | 10.15 | 33.31 | 0.5 mm² |
| 21 | 0.02846 | 0.7229 | 0.8101 | 0.4105 | 12.80 | 42.00 | 0.5 mm² |
| 22 | 0.02535 | 0.6438 | 0.6424 | 0.3255 | 16.14 | 52.96 | – |
| 23 | 0.02257 | 0.5733 | 0.5095 | 0.2582 | 20.36 | 66.78 | – |
| 24 | 0.02010 | 0.5106 | 0.4040 | 0.2047 | 25.67 | 84.21 | – |
| 25 | 0.01790 | 0.4547 | 0.3204 | 0.1624 | 32.37 | 106.2 | – |
| 26 | 0.01594 | 0.4049 | 0.2541 | 0.1288 | 40.81 | 133.9 | – |
| 27 | 0.01420 | 0.3606 | 0.2015 | 0.1021 | 51.47 | 168.9 | – |
| 28 | 0.01264 | 0.3211 | 0.1598 | 0.08098 | 64.90 | 212.9 | – |
| 29 | 0.01126 | 0.2859 | 0.1267 | 0.06422 | 81.83 | 268.5 | – |
| 30 | 0.01003 | 0.2546 | 0.1005 | 0.05093 | 103.2 | 338.5 | – |
| 31 | 0.008928 | 0.2268 | 0.07970 | 0.04039 | 130.1 | 426.9 | – |
| 32 | 0.007950 | 0.2019 | 0.06321 | 0.03203 | 164.1 | 538.3 | – |
| 33 | 0.007080 | 0.1798 | 0.05013 | 0.02540 | 206.9 | 678.8 | – |
| 34 | 0.006305 | 0.1601 | 0.03975 | 0.02014 | 260.9 | 856.0 | – |
| 35 | 0.005615 | 0.1426 | 0.03152 | 0.01597 | 329.0 | 1,079 | – |
| 36 | 0.005000 | 0.1270 | 0.02500 | 0.01267 | 414.8 | 1,361 | – |
| 37 | 0.004453 | 0.1131 | 0.01983 | 0.01005 | 523.1 | 1,716 | – |
| 38 | 0.003965 | 0.1007 | 0.01572 | 0.007967 | 659.6 | 2,164 | – |
| 39 | 0.003531 | 0.08969 | 0.01247 | 0.006318 | 831.8 | 2,729 | – |
| 40 | 0.003145 | 0.07987 | 0.009888 | 0.005010 | 1,049 | 3,441 | – |
Solid annealed copper at 20 °C (ρ = 1.7241 × 10⁻⁸ Ω·m, 100 % IACS). d = 0.005 in × 92(36 − n)/39; 0000 = n −3. Stranded wire is about 2–3 % larger in diameter and slightly higher in resistance (NEC Chapter 9, Table 8). Nearest metric = closest IEC size by area (within ±30 %), not an equivalent ampacity.
Frequently asked questions
What is an acceptable voltage drop?
3% or less on a branch circuit or feeder, and 5% or less in total, per the NEC informational notes.
Does voltage drop depend on voltage?
The volts lost depend only on current, length and wire. But the percentage is much smaller at higher voltage, which is why long runs use 240 V or 480 V.
How do I reduce voltage drop?
Use a larger wire, shorten the run, raise the system voltage, or split the load across more circuits.