Voltage Drop Calculator

Check how many volts a wire loses over distance, and whether it stays within the recommended 3%.

Free, no sign-upInstant resultsUpdated October 2026
Conductor
A
Phase
Voltage drop
–
How we calculated this

    For estimating and educational purposes only. Results are approximate and are not a substitute for a licensed professional, the manufacturer's instructions or your local code. Disclaimer

    Embed this calculator on your site

    Free for any website or blog. Copy the code below and paste it into an HTML block. Keep the credit link.

    Power line running across the countryside
    Power line running across the countrysidePhoto: Jaël Vallée / Unsplash

    What is voltage drop?

    Every wire has resistance, so some voltage is lost as current flows through it. The longer the run and the higher the current, the bigger the loss. Too much drop makes motors run hot, LEDs flicker and chargers slow down.

    Voltage drop formula

    Single-phase: VD = 2 × L × I × R ÷ 1000 Three-phase: VD = 1.732 × L × I × R ÷ 1000 Percent drop: VD% = VD ÷ Source volts × 100

    L is the one-way length in feet, I is the current in amps, and R is the conductor resistance in ohms per 1,000 ft from NEC Chapter 9, Table 8.

    Example

    10 AWG copper, 24 A, 100 ft, 240 V single-phase: 2 × 100 × 24 × 1.21 ÷ 1000 = 5.81 V, which is 2.42%. That is within the 3% recommendation.

    Recommended limits

    The NEC informational notes in 210.19 and 215.2 recommend no more than 3% on a branch circuit or feeder and 5% total from the service to the farthest outlet. These are recommendations, but many inspectors and equipment manufacturers expect them.

    Resistance per 1,000 ft (NEC Ch. 9, Table 8)

    SizeCopper ΩAluminum Ω
    14 AWG3.07–
    12 AWG1.933.18
    10 AWG1.212.00
    8 AWG0.7641.26
    6 AWG0.4910.808
    4 AWG0.3080.508
    2 AWG0.1940.319
    1/0 AWG0.1220.201
    2/0 AWG0.09670.159
    4/0 AWG0.06080.100

    Maximum wire length for 3% voltage drop at 120 V

    Longest one-way run (in feet) for each copper wire size and load current before the voltage drop reaches 3% on a 120 V single-phase circuit.

    Show full table
    AWG10 A15 A20 A30 A40 A50 A60 A80 A100 A150 A200 A
    1459 ft39 ft–––––––––
    1293 ft62 ft47 ft––––––––
    10149 ft99 ft74 ft50 ft–––––––
    8236 ft157 ft118 ft79 ft59 ft47 ft–––––
    6367 ft244 ft183 ft122 ft92 ft73 ft61 ft––––
    4584 ft390 ft292 ft195 ft146 ft117 ft97 ft73 ft–––
    3735 ft490 ft367 ft245 ft184 ft147 ft122 ft92 ft73 ft––
    2928 ft619 ft464 ft309 ft232 ft186 ft155 ft116 ft93 ft––
    11,169 ft779 ft584 ft390 ft292 ft234 ft195 ft146 ft117 ft––
    1/01,475 ft984 ft738 ft492 ft369 ft295 ft246 ft184 ft148 ft98 ft–
    2/01,861 ft1,241 ft931 ft620 ft465 ft372 ft310 ft233 ft186 ft124 ft–
    3/02,350 ft1,567 ft1,175 ft783 ft587 ft470 ft392 ft294 ft235 ft157 ft117 ft
    4/02,961 ft1,974 ft1,480 ft987 ft740 ft592 ft493 ft370 ft296 ft197 ft148 ft

    Copper, NEC Chapter 9 Table 8 resistance (75 °C), power factor 1: L = 0.03 × V × 1000 ÷ (2 × I × RΩ/kft). “–” = current above the wire's 75 °C ampacity (or the 240.4(D) limit). For a 5% limit multiply by 5/3; for aluminum divide by about 1.65.

    Maximum wire length for 3% voltage drop at 240 V

    Longest one-way run (in feet) for each copper wire size and load current before the voltage drop reaches 3% on a 240 V single-phase circuit.

    Show full table
    AWG10 A15 A20 A30 A40 A50 A60 A80 A100 A150 A200 A
    14117 ft78 ft–––––––––
    12187 ft124 ft93 ft––––––––
    10298 ft198 ft149 ft99 ft–––––––
    8471 ft314 ft236 ft157 ft118 ft94 ft–––––
    6733 ft489 ft367 ft244 ft183 ft147 ft122 ft––––
    41,169 ft779 ft584 ft390 ft292 ft234 ft195 ft146 ft–––
    31,469 ft980 ft735 ft490 ft367 ft294 ft245 ft184 ft147 ft––
    21,856 ft1,237 ft928 ft619 ft464 ft371 ft309 ft232 ft186 ft––
    12,338 ft1,558 ft1,169 ft779 ft584 ft468 ft390 ft292 ft234 ft––
    1/02,951 ft1,967 ft1,475 ft984 ft738 ft590 ft492 ft369 ft295 ft197 ft–
    2/03,723 ft2,482 ft1,861 ft1,241 ft931 ft745 ft620 ft465 ft372 ft248 ft–
    3/04,700 ft3,133 ft2,350 ft1,567 ft1,175 ft940 ft783 ft587 ft470 ft313 ft235 ft
    4/05,921 ft3,947 ft2,961 ft1,974 ft1,480 ft1,184 ft987 ft740 ft592 ft395 ft296 ft

    Copper, NEC Chapter 9 Table 8 resistance (75 °C), power factor 1: L = 0.03 × V × 1000 ÷ (2 × I × RΩ/kft). “–” = current above the wire's 75 °C ampacity (or the 240.4(D) limit). For a 5% limit multiply by 5/3; for aluminum divide by about 1.65.

    AWG wire gauge chart: 4/0 to 40 AWG

    Diameter, cross-section and copper resistance for every American Wire Gauge size from 0000 down to 40, computed from the exact AWG definition.

    Show full table
    AWGDiameter (in)Diameter (mm)Area (kcmil)Area (mm²)Cu Ω/1000 ftCu Ω/kmNearest metric
    4/0 (0000)0.460011.68211.6107.20.049010.1608120 mm²
    3/0 (000)0.409610.40167.885.030.061800.202895 mm²
    2/0 (00)0.36489.266133.167.430.077930.255770 mm²
    1/0 (0)0.32498.251105.553.480.098270.322450 mm²
    10.28937.34883.6942.410.12390.406650 mm²
    20.25766.54466.3733.630.15630.512735 mm²
    30.22945.82752.6326.670.19700.646425 mm²
    40.20435.18941.7421.150.24850.815225 mm²
    50.18194.62133.1016.770.31331.02816 mm²
    60.16204.11526.2513.300.39511.29616 mm²
    70.14433.66520.8210.550.49821.63410 mm²
    80.12853.26416.518.3660.62822.06110 mm²
    90.11442.90613.096.6340.79212.5996 mm²
    100.10192.58810.385.2610.99883.2776 mm²
    110.090742.3058.2344.1721.2604.1324 mm²
    120.080812.0536.5303.3091.5885.2114 mm²
    130.071961.8285.1782.6242.0036.5712.5 mm²
    140.064081.6284.1072.0812.5258.2852.5 mm²
    150.057071.4503.2571.6503.18410.451.5 mm²
    160.050821.2912.5831.3094.01513.171.5 mm²
    170.045261.1502.0481.0385.06316.611 mm²
    180.040301.0241.6240.82306.38520.950.75 mm²
    190.035890.91161.2880.65278.05126.410.75 mm²
    200.031960.81181.0220.517610.1533.310.5 mm²
    210.028460.72290.81010.410512.8042.000.5 mm²
    220.025350.64380.64240.325516.1452.96–
    230.022570.57330.50950.258220.3666.78–
    240.020100.51060.40400.204725.6784.21–
    250.017900.45470.32040.162432.37106.2–
    260.015940.40490.25410.128840.81133.9–
    270.014200.36060.20150.102151.47168.9–
    280.012640.32110.15980.0809864.90212.9–
    290.011260.28590.12670.0642281.83268.5–
    300.010030.25460.10050.05093103.2338.5–
    310.0089280.22680.079700.04039130.1426.9–
    320.0079500.20190.063210.03203164.1538.3–
    330.0070800.17980.050130.02540206.9678.8–
    340.0063050.16010.039750.02014260.9856.0–
    350.0056150.14260.031520.01597329.01,079–
    360.0050000.12700.025000.01267414.81,361–
    370.0044530.11310.019830.01005523.11,716–
    380.0039650.10070.015720.007967659.62,164–
    390.0035310.089690.012470.006318831.82,729–
    400.0031450.079870.0098880.0050101,0493,441–

    Solid annealed copper at 20 °C (ρ = 1.7241 × 10⁻⁸ Ω·m, 100 % IACS). d = 0.005 in × 92(36 − n)/39; 0000 = n −3. Stranded wire is about 2–3 % larger in diameter and slightly higher in resistance (NEC Chapter 9, Table 8). Nearest metric = closest IEC size by area (within ±30 %), not an equivalent ampacity.

    Frequently asked questions

    What is an acceptable voltage drop?

    3% or less on a branch circuit or feeder, and 5% or less in total, per the NEC informational notes.

    Does voltage drop depend on voltage?

    The volts lost depend only on current, length and wire. But the percentage is much smaller at higher voltage, which is why long runs use 240 V or 480 V.

    How do I reduce voltage drop?

    Use a larger wire, shorten the run, raise the system voltage, or split the load across more circuits.