UPS Runtime Calculator

Estimate battery backup time for a computer, NVR or network rack, and check the UPS size.

Free, no sign-upInstant resultsUpdated October 2026
W
Sum of connected equipment.
W
Optional: 0 to skip.
V
Two 12 V batteries = 24 V.
Ah
%
Runtime
–
How we calculated this

    For estimating and educational purposes only. Results are approximate and are not a substitute for a licensed professional, the manufacturer's instructions or your local code. Disclaimer

    Embed this calculator on your site

    Free for any website or blog. Copy the code below and paste it into an HTML block. Keep the credit link.

    Transmission tower under a cloudy sky
    Transmission tower under a cloudy skyPhoto: CHRSNDRSN / Unsplash

    How UPS runtime is estimated

    Divide the load by the battery voltage and inverter efficiency to find the battery current. Small sealed lead-acid batteries deliver far less than their rated amp-hours at high current (the Peukert effect), so we scale the 20-hour rating accordingly.

    Battery current I = Load W ÷ (Battery V × Efficiency) Runtime (h) = 20 × (Ah ÷ (I × 20))^1.2

    Example: 300 W on a 1500 VA UPS with two 12 V 9 Ah batteries

    I = 300 ÷ (24 × 0.9) = 13.9 A. Runtime = 20 × (9 ÷ 278)^1.2 = 0.33 h, about 20 minutes.

    Sizing a UPS

    • Keep the load under 80% of the UPS's watt rating, not just its VA rating.
    • VA ≈ W ÷ power factor. Modern PC power supplies have a power factor of about 0.9–0.99.
    • For longer runtime, add an external battery pack rather than a bigger UPS.
    • Lead-acid UPS batteries typically last 3–5 years.

    UPS runtime chart by battery and load

    Estimated backup time of a UPS with sealed lead-acid batteries for common battery packs and loads, using the same Peukert model as the calculator.

    Show full table
    Battery pack50 W100 W150 W200 W300 W400 W500 W750 W1,000 W1,500 W
    1 × 12 V 7 Ah
    12 V · 84 Wh
    54 min24 min14 min10 min6 min4 min3 min2 min1 min1 min
    1 × 12 V 9 Ah
    12 V · 108 Wh
    73 min32 min20 min14 min9 min6 min5 min3 min2 min1 min
    2 × 12 V 7 Ah
    24 V · 168 Wh
    2.1 h54 min33 min24 min14 min10 min8 min5 min3 min2 min
    2 × 12 V 9 Ah
    24 V · 216 Wh
    2.8 h73 min45 min32 min20 min14 min11 min7 min5 min3 min
    3 × 12 V 9 Ah
    36 V · 324 Wh
    4.6 h119 min73 min52 min32 min23 min17 min11 min8 min5 min
    4 × 12 V 9 Ah
    48 V · 432 Wh
    6.4 h2.8 h103 min73 min45 min32 min24 min15 min11 min7 min
    2 × 12 V 18 Ah
    24 V · 432 Wh
    6.4 h2.8 h103 min73 min45 min32 min24 min15 min11 min7 min
    4 × 12 V 18 Ah
    48 V · 864 Wh
    14.8 h6.4 h4.0 h2.8 h103 min73 min56 min34 min24 min15 min
    6 × 12 V 9 Ah
    72 V · 648 Wh
    10.5 h4.6 h2.8 h119 min73 min52 min40 min24 min17 min11 min
    8 × 12 V 9 Ah
    96 V · 864 Wh
    14.8 h6.4 h4.0 h2.8 h103 min73 min56 min34 min24 min15 min

    I = W ÷ (V × 90%); runtime = 20 h × (Ah ÷ (I × 20))1.2 (Peukert exponent 1.2 on the 20-hour rating). Typical packs: 600–850 VA = 1 × 12 V 7–9 Ah; 1000–1500 VA = 2 × 12 V 7–9 Ah; 2200–3000 VA = 4–8 × 12 V 9 Ah. A load above about 80% of the UPS watt rating is not allowed even if a time is shown. Batteries lose about 20–40% of their runtime after 3–4 years.

    Frequently asked questions

    How long will a 1500VA UPS last?

    With two 9 Ah batteries, about 20 minutes at 300 W and 5–8 minutes at 700 W.

    What is the difference between VA and watts on a UPS?

    VA is apparent power; watts is real power. The UPS must meet both ratings for your load.

    Why is runtime not linear with load?

    Lead-acid capacity drops at higher discharge rates, so doubling the load more than halves the runtime.