How UPS runtime is estimated
Divide the load by the battery voltage and inverter efficiency to find the battery current. Small sealed lead-acid batteries deliver far less than their rated amp-hours at high current (the Peukert effect), so we scale the 20-hour rating accordingly.
Example: 300 W on a 1500 VA UPS with two 12 V 9 Ah batteries
I = 300 ÷ (24 × 0.9) = 13.9 A. Runtime = 20 × (9 ÷ 278)^1.2 = 0.33 h, about 20 minutes.
Sizing a UPS
- Keep the load under 80% of the UPS's watt rating, not just its VA rating.
- VA ≈ W ÷ power factor. Modern PC power supplies have a power factor of about 0.9–0.99.
- For longer runtime, add an external battery pack rather than a bigger UPS.
- Lead-acid UPS batteries typically last 3–5 years.
UPS runtime chart by battery and load
Estimated backup time of a UPS with sealed lead-acid batteries for common battery packs and loads, using the same Peukert model as the calculator.
Show full table
| Battery pack | 50 W | 100 W | 150 W | 200 W | 300 W | 400 W | 500 W | 750 W | 1,000 W | 1,500 W |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 × 12 V 7 Ah 12 V · 84 Wh | 54 min | 24 min | 14 min | 10 min | 6 min | 4 min | 3 min | 2 min | 1 min | 1 min |
| 1 × 12 V 9 Ah 12 V · 108 Wh | 73 min | 32 min | 20 min | 14 min | 9 min | 6 min | 5 min | 3 min | 2 min | 1 min |
| 2 × 12 V 7 Ah 24 V · 168 Wh | 2.1 h | 54 min | 33 min | 24 min | 14 min | 10 min | 8 min | 5 min | 3 min | 2 min |
| 2 × 12 V 9 Ah 24 V · 216 Wh | 2.8 h | 73 min | 45 min | 32 min | 20 min | 14 min | 11 min | 7 min | 5 min | 3 min |
| 3 × 12 V 9 Ah 36 V · 324 Wh | 4.6 h | 119 min | 73 min | 52 min | 32 min | 23 min | 17 min | 11 min | 8 min | 5 min |
| 4 × 12 V 9 Ah 48 V · 432 Wh | 6.4 h | 2.8 h | 103 min | 73 min | 45 min | 32 min | 24 min | 15 min | 11 min | 7 min |
| 2 × 12 V 18 Ah 24 V · 432 Wh | 6.4 h | 2.8 h | 103 min | 73 min | 45 min | 32 min | 24 min | 15 min | 11 min | 7 min |
| 4 × 12 V 18 Ah 48 V · 864 Wh | 14.8 h | 6.4 h | 4.0 h | 2.8 h | 103 min | 73 min | 56 min | 34 min | 24 min | 15 min |
| 6 × 12 V 9 Ah 72 V · 648 Wh | 10.5 h | 4.6 h | 2.8 h | 119 min | 73 min | 52 min | 40 min | 24 min | 17 min | 11 min |
| 8 × 12 V 9 Ah 96 V · 864 Wh | 14.8 h | 6.4 h | 4.0 h | 2.8 h | 103 min | 73 min | 56 min | 34 min | 24 min | 15 min |
I = W ÷ (V × 90%); runtime = 20 h × (Ah ÷ (I × 20))1.2 (Peukert exponent 1.2 on the 20-hour rating). Typical packs: 600–850 VA = 1 × 12 V 7–9 Ah; 1000–1500 VA = 2 × 12 V 7–9 Ah; 2200–3000 VA = 4–8 × 12 V 9 Ah. A load above about 80% of the UPS watt rating is not allowed even if a time is shown. Batteries lose about 20–40% of their runtime after 3–4 years.
Frequently asked questions
How long will a 1500VA UPS last?
With two 9 Ah batteries, about 20 minutes at 300 W and 5–8 minutes at 700 W.
What is the difference between VA and watts on a UPS?
VA is apparent power; watts is real power. The UPS must meet both ratings for your load.
Why is runtime not linear with load?
Lead-acid capacity drops at higher discharge rates, so doubling the load more than halves the runtime.