3/0 AWG specifications
| Property | Value |
|---|---|
| Area | 85.03 mm² |
| Circular mils | 167,806 |
| Diameter (solid) | 10.40 mm / 0.4096 in |
| Resistance, copper, 20 °C | 0.203 Ω/km · 0.062 Ω/1000 ft |
| Ampacity, copper 75°C (NEC 310.16) | 200 A |
| Nearest metric size | 95 mm² |
Diameter from the AWG formula d = 0.127 × 92^((36 − n) ÷ 39) mm. Stranded wire has a slightly larger outside diameter.
Frequently asked questions
What is 3/0 AWG in mm²?
85.03 mm².
What metric cable replaces 3/0 AWG?
95 mm², the next standard size up.