The case: a hardwired 5,000-watt fan-forced garage heater, 240 V single-phase, copper wire, mounted about 60 ft (one way) from the main panel. The owner wants the shop usable on winter weekends.
Short answer: the heater draws 20.8 A. Fixed space heating is sized at 125%, so the circuit needs 26.0 A of capacity: a 30 A two-pole breaker and 10 AWG copper (10/2 NM-B with ground, or THHN in conduit). Voltage drop at 60 ft is only 1.26%.
1. Start with the current: watts ÷ volts
A resistance heater is the easiest load in the house to calculate. It has no motor inrush worth worrying about and a power factor of 1, so the current is simply power divided by voltage:
5,000 W ÷ 240 V = 20.83 A
Fan-forced garage heaters do have a small blower motor, but on a typical 5 kW unit it adds only a fraction of an amp. The nameplate current already includes it, so always use the amps printed on the label when they are given.
The same heater produces about 17,060 BTU/h (1 W = 3.412 BTU/h). That is a useful number when you compare it with a propane unit or a mini-split rated in BTU.
2. Apply the 125% rule for fixed space heating
The NEC treats fixed electric space-heating equipment as a continuous load. NEC 424.4(B) (424.3(B) in editions before 2020) requires the branch-circuit conductors and the overcurrent device to be sized at at least 125% of the heater load.
20.83 A × 1.25 = 26.04 A
The next standard breaker size is 30 A. A 25 A breaker is a standard size too, but it is below 26.0 A, so it is not allowed here.
This is the step most people skip. They see "21 amps", reach for a 25 A breaker and 12-gauge wire, and end up with a circuit that runs hot for hours on a cold night and trips the breaker over and over.
3. Pick the wire by ampacity
The conductor must be protected by the 30 A breaker and carry at least 26.0 A. Two rules decide the size:
- NEC 240.4(D) caps the breaker for small copper conductors: 14 AWG at 15 A, 12 AWG at 20 A and 10 AWG at 30 A. 12 AWG is out.
- NM-B (Romex) cable must be sized from the 60 °C column of NEC Table 310.16, where 10 AWG copper is rated 30 A. That matches the breaker exactly.
So 10/2 NM-B with ground works in a finished or protected wall. In an unfinished garage where the cable would be exposed to damage, run THHN/THWN-2 in conduit; 10 AWG is still the answer.
A 240 V heater needs no neutral. In 10/2 cable the white conductor is used as a second hot, and NEC 200.7(C) requires it to be re-identified with black or red tape at both ends.
4. Check voltage drop over the real distance
Voltage drop is rarely the problem on a 21 A load, but long runs to detached garages and pole barns are where it starts to matter. The NEC recommends keeping branch-circuit drop near 3% (informational note to 210.19).
| One-way run | Wire that meets ampacity and 3% | Voltage drop |
|---|---|---|
| 60 ft | 10 AWG | 1.26% |
| 100 ft | 10 AWG | 2.10% |
| 150 ft | 8 AWG | 1.99% |
| 200 ft | 8 AWG | 2.65% |
A heater does not fail when the voltage sags, it just makes less heat. Resistance heat scales with the square of the voltage, so every percent of drop costs about two percent of output. That is another reason not to undersize a long run.
5. Breaker and wire by heater size
Garage heaters are sold in a handful of standard sizes. Same rules, same 60 ft run:
| Heater | Current at 240 V | 125% | Breaker | Copper wire | Heat output |
|---|---|---|---|---|---|
| 4,000 W | 16.7 A | 20.8 A | 25 A | 10 AWG | 13,648 BTU/h |
| 5,000 W | 20.8 A | 26.0 A | 30 A | 10 AWG | 17,060 BTU/h |
| 7,500 W | 31.3 A | 39.1 A | 40 A | 8 AWG | 25,590 BTU/h |
| 10,000 W | 41.7 A | 52.1 A | 60 A | 6 AWG | 34,120 BTU/h |
The wire column assumes THHN/THWN-2 in conduit on 75 °C terminals. With NM-B cable you must use the 60 °C column: 8 AWG NM-B is rated 40 A and still works for the 7,500 W heater, but the 10,000 W heater needs 4 AWG NM-B, because 6 AWG NM-B is only good for 55 A.
Notice the jump from 5,000 W to 7,500 W: the breaker goes from 30 A to 40 A and the wire from 10 AWG to 8 AWG. If you are pulling new cable anyway and might upgrade later, running the larger wire now costs much less than pulling it twice. Just remember the breaker must still match the heater's instructions: oversized wire is fine, an oversized breaker is not.
6. How to read the heater label
Before you buy wire, read the nameplate or the installation manual. Look for:
- Rated watts and volts. Many units list two ratings, for example 5,000 W at 240 V and a lower number at 208 V.
- Amps. Use this figure for the 125% calculation if it is printed.
- Maximum overcurrent protection or a recommended breaker. If the manual gives one, it overrides a generic table.
- "Use copper conductors only" and the terminal temperature rating. Most heater terminal blocks are copper-only.
- Mounting clearances from the floor, ceiling and side walls, and a warning not to mount it where a car door or a lift can hit it.
The 208 V trap. In apartments, condos and many commercial buildings, the supply is 208 V, not 240 V. A heater rated 5,000 W at 240 V delivers only about 3,756 W at 208 V and draws 18.1 A. The circuit size does not change much, but you get roughly a quarter less heat. Measure the voltage at the panel before you choose the model.
7. Installation and inspection checklist
- Dedicated circuit: no garage receptacles or lights on the heater breaker.
- Breaker: 30 A two-pole, same brand and type as the panel.
- Wire: 10 AWG copper, white conductor re-marked as a hot.
- Equipment grounding conductor landed on the heater's ground screw and the panel's ground bar.
- Disconnecting means as required by NEC 424.19: often a lockable breaker or a disconnect within sight of the heater, unless the unit's built-in thermostat with a marked "off" position qualifies. Check with your inspector.
- If you use a plug and receptacle instead of hardwiring: recent NEC editions require GFCI protection for 240 V receptacles in garages, so you would need a two-pole GFCI breaker.
- Mount at the height and clearances in the manual, away from gasoline cans, solvents and sawdust.
- Pull a permit if your jurisdiction requires one for a new circuit (most do).
8. Signs of a problem
- Breaker trips after 30 to 60 minutes, not instantly: the breaker is too small for a continuous load, or a loose connection is heating it.
- Discolored or warm breaker, burnt smell at the panel: stop using the heater and have the terminal checked and torqued.
- Heater blows lukewarm air on a long run: measure the voltage at the heater while it runs; a big difference from the panel reading points to undersized wire or a bad splice.
- Lights dim when the heater cycles: normal for a split second on a weak service, worrying if it lasts.
Common mistakes
- Using 12 AWG on a 25 A breaker. 240.4(D) limits 12 AWG copper to 20 A, and the 125% rule already demands 26.0 A.
- Ignoring the 125% rule. A 20.8 A heater on a 25 A breaker is under code minimum.
- Assuming 240 V. On 208 V service you lose about a quarter of the rated heat.
- Sharing the circuit. A compressor or a table saw on the same breaker will trip it on the first cold morning.
- Aluminum wire on copper-only terminals. Read the label before buying a cheaper cable.
FAQ
Can I run a 5,000 W heater on a 30 A breaker with 10 gauge wire? Yes. The heater draws 20.8 A, 125% of that is 26.0 A, and a 30 A breaker with 10 AWG copper covers it.
Can I use a 25 A breaker instead? No. 25 A is below the 26.0 A that the 125% rule demands for fixed space heating.
How much does it cost to run a 5,000 W garage heater? It uses 5 kWh for every hour it actually runs. At an example rate of $0.18/kWh and 6 hours of real run time per day, that is 30 kWh and about $5.40 a day, or roughly $162 a month. Use your own utility rate; the thermostat duty cycle drops sharply in an insulated garage.
What size breaker for a 7,500 W garage heater? It draws 31.3 A; at 125% that is 39.1 A, so a 40 A breaker with 8 AWG copper.
Does a 240 V heater need a neutral? No. Two hots and an equipment ground. Use 10/2 cable with ground and re-mark the white conductor.
My garage is 200 ft from the panel. Does 10 AWG still work? Not at the 3% target. At 200 ft you need 8 AWG, with a voltage drop of 2.65%. For runs that long, a subpanel in the garage is often the better plan.
Summary
| Item | 5,000 W heater, 60 ft, 240 V |
|---|---|
| Heater current | 20.8 A |
| 125% continuous load | 26.0 A |
| Breaker | 30 A two-pole |
| Copper wire | 10 AWG (10/2 NM-B with ground or THHN) |
| Voltage drop at 60 ft | 1.26% |
| Heat output | 17,060 BTU/h |
| Output at 208 V | about 3,756 W |
Have a different heater, voltage or distance? Enter it in the SizeBench wire size calculator and get the breaker, wire and voltage drop in one step.
Try it with your own numbersWire Size Calculator→Sources and references
- NFPA 70, National Electrical Code (NEC) 424.4(B) (125% for fixed space heating), 424.19 (disconnecting means), 240.4(D) (small conductors), Table 310.16 and 334.80 (NM-B at 60 °C), 200.7(C) (re-identifying white conductor), 210.8 (GFCI in garages)
- EC&M – Code Basics: Article 424, Fixed Electric Space Heating overview of Article 424 requirements used to explain the continuous-load sizing and disconnect rules
- U.S. Department of Energy – Energy Saver: Electric Resistance Heating background on resistance heaters: 100% conversion of electricity to heat and running-cost context
- U.S. Energy Information Administration – Electric Power Monthly, average retail price reference for readers to look up their state's residential rate (our $0.18/kWh is only an example)
- SizeBench – Wire Size Calculator calculator used for ampacity, breaker and voltage drop
Standards and data behind our calculators
How we made this guide
Every number in this guide is calculated by the same code as our calculators, from the standards listed above, and the page is tested before publication. Redação Grupo TAAP wrote it; we use automation and AI tools to help draft, never to produce the figures. Thiago André Azevedo Pires, managing editor, reviewed and approved it before publication. Methodology and sources →
Revision history
- · Published
- · Reviewed