6 AWG specifications
| Property | Value |
|---|---|
| Area | 13.30 mm² |
| Circular mils | 26,251 |
| Diameter (solid) | 4.12 mm / 0.1620 in |
| Resistance, copper, 20 °C | 1.296 Ω/km · 0.395 Ω/1000 ft |
| Ampacity, copper 75°C (NEC 310.16) | 65 A |
| Nearest metric size | 16 mm² |
Diameter from the AWG formula d = 0.127 × 92^((36 − n) ÷ 39) mm. Stranded wire has a slightly larger outside diameter.
Frequently asked questions
What is 6 AWG in mm²?
13.30 mm².
What metric cable replaces 6 AWG?
16 mm², the next standard size up.