The case: a whole-house electric tankless water heater rated 27 kW at 240 V, built with 3 heating elements of 9 kW each. The panel is 40 ft away, the house has a 200 A service, and the family lives where the cold-water line drops to about 40 °F in January.
Short answer: the heater draws 112.5 A in total, split into 3 circuits of 37.5 A. The usual layout is 3 two-pole 40 A breakers with 8 AWG copper on each circuit (voltage drop 0.96% at 40 ft). In winter it delivers about 2.8 GPM at a 105 °F shower: one shower at a time, not two.
Electric tankless heaters sell on a simple promise: endless hot water, no tank, no flue. The first cold snap is when owners find out what the label really means. The heater did not get weaker. The water coming in got colder, and the same kilowatts now heat less of it. This guide walks through both halves of the problem, the electrical circuits and the flow rate, using the numbers an electrician and a plumber would use.
1. Turn kilowatts into amps
Every element is a resistive load, so the math is plain Ohm's law: I = P ÷ V.
- Whole heater: 27,000 W ÷ 240 V = 112.5 A
- Each element: 9,000 W ÷ 240 V = 37.5 A
No single residential branch circuit is meant to carry 113 A, which is why large units split the load. Each element gets its own two-pole breaker and its own pair of conductors, and the heater's terminal block has a separate set of lugs for each circuit. The label and the installation manual list how many circuits the model needs and the breaker size for each one.
2. Pick the breaker for each circuit
The NEC requires the branch circuit to be rated at least as high as the appliance's marked rating, and it requires you to follow the listing and the manufacturer's instructions (NEC 110.3(B)). The 125% continuous-load rule that people remember from water heaters is written for storage-type heaters of 120 gallons or less (NEC 422.13). A tankless unit has no storage, so most manufacturers size the breaker at the next standard size above the element current:
37.5 A → 40 A two-pole breaker
Some inspectors still treat a tankless heater as a continuous load, especially on units that can run for long stretches filling a tub or feeding radiant floors. With 125% applied, the math changes:
37.5 A × 1.25 = 46.9 A → 50 A two-pole breaker
Never go bigger than the maximum overcurrent device printed on the label, and ask your inspector before you buy breakers. It is a two-minute phone call that can save a failed inspection.
| Layout | Current per circuit | Breaker | Copper wire (THHN, 75 °C) | NM-B cable (60 °C) |
|---|---|---|---|---|
| Manufacturer sizing | 37.5 A | 40 A | 8 AWG | 8 AWG |
| 125% continuous sizing | 46.9 A | 50 A | 8 AWG | 6 AWG |
3. Size the wire, then check the distance
From NEC Table 310.16, 8 AWG copper is good for 40 A in the 60 °C column (NM-B, NEC 334.80) and 50 A in the 75 °C column (THHN/THWN-2 on 75 °C terminals). Both clear a 40 A breaker. On the 125% layout, 50 A needs 8 AWG THHN in conduit or 6 AWG NM-B.
Voltage drop rarely decides the size on a heater mounted near the panel, but it can when the heater sits in a far bathroom or a detached suite. With the NEC's 3% target:
| One-way run | Wire that meets ampacity and 3% | Voltage drop |
|---|---|---|
| 40 ft | 8 AWG | 0.96% |
| 100 ft | 8 AWG | 2.39% |
| 150 ft | 6 AWG | 2.30% |
A heater that sees low voltage still works, but it heats less: a resistive element's power falls with the square of the voltage. A 3% drop costs roughly 6% of the heating power, which shows up as a cooler shower on the coldest morning of the year.
Each circuit also needs an equipment grounding conductor: 10 AWG copper covers both the 40 A and the 50 A layouts (NEC Table 250.122).
4. Check the service before anything else
The three circuits together add 112.5 A at 240 V, about 56% of a 200 A service, and all of it can switch on at once the moment someone opens a hot tap. That is the real constraint on whole-house electric tankless heaters.
Before buying the heater, someone has to run a load calculation under NEC Article 220 with every major appliance in the house: range, dryer, heat pump or furnace blower, EV charger. Homes with gas heat and gas cooking often pass on 200 A. Homes on 100 A almost never do with a unit this size. If the calculation fails, the honest options are a smaller point-of-use unit, a heat pump water heater, or a service upgrade.
5. Flow rate: what the kilowatts buy you
Heating water takes about 500 BTU per hour for every gallon per minute and every degree Fahrenheit of rise (8.33 lb per gallon × 60 minutes). One kilowatt is 3,412 BTU/h, so:
GPM = kW × 3,412 ÷ (500 × temperature rise)
For a 105 °F shower, the rise depends on the season and the region:
| Incoming water | Rise to 105 °F | Flow from 27 kW |
|---|---|---|
| 40 °F (northern winter) | 65 °F | 2.83 GPM |
| 55 °F (mild climate) | 50 °F | 3.68 GPM |
| 70 °F (southern summer) | 35 °F | 5.26 GPM |
The federal maximum for a showerhead is 2.5 GPM, and WaterSense-labeled heads use 2.0 GPM or less. In a northern January, 2.8 GPM covers one shower with a little to spare for a sink. Two 2.0 GPM showers at the same time need 38.1 kW at a 65 °F rise, more than this heater has. In a southern summer the same unit delivers 5.3 GPM and two showers are easy, which is why reviews of the same model can sound like they describe two different products.
6. How to read the label
The rating plate and the manual give you everything this calculation needs. Look for:
- Rated power and voltage: "27 kW at 240 V". At 208 V, common in apartments with three-phase service, the same elements produce about 75% of the rated power, since power scales with the square of voltage.
- Number of circuits and amps per circuit: for this unit, 3 × 37.5 A.
- Maximum overcurrent protection: the largest breaker allowed per circuit.
- Minimum conductor size and temperature rating: some units require 75 °C wire and terminals.
- Minimum activation flow: the smallest flow that turns the elements on, often a fraction of a gallon per minute. Low-flow faucets can fall below it.
7. Installation and inspection checklist
- [ ] Load calculation shows the service can carry 112.5 A of new load
- [ ] 3 separate two-pole breakers, each sized per the label (40 A, or 50 A if your inspector applies 125%)
- [ ] Wire size matches the method: 8 AWG THHN or 8 AWG NM-B at 40 A; 8 AWG THHN or 6 AWG NM-B at 50 A
- [ ] Each circuit lands on its own lugs at the heater, with the grounding conductor bonded
- [ ] Terminals torqued to the value on the label, then checked again after the first heating cycles
- [ ] Disconnecting means within sight of the heater, or a breaker that can be locked off
- [ ] Water lines flushed and the unit filled with water before the breakers are turned on
The last line is there for a reason: energizing a dry element can burn it out in seconds.
8. Signs of a problem
- Lukewarm water only in winter: the heater is at full power and the rise is too high for the flow. Reduce the flow or accept a lower temperature.
- Water that cycles hot and cold: often flow near the activation threshold, or a mixing valve that is starving the heater.
- Lights dimming when the hot water runs: a large voltage drop in the service or the feeder. Have it measured under load.
- Warm breakers, discolored insulation or a burning smell: loose terminals. Shut the circuits off and call an electrician.
- One element never heating: check that circuit's breaker first, then the element.
Common mistakes
- One big breaker for the whole heater. A 113 A load on a single circuit is not how these units are listed. Use the circuits the manual shows.
- Reusing the old water heater circuit. A 30 A circuit from a tank heater cannot feed even one 9 kW element.
- Sizing for summer. The flow table above is the real sizing tool. Size for your coldest incoming water.
- Skipping the load calculation. Most failed installs of large tankless units fail on service capacity, not on wire.
- Low-flow fixtures below the activation flow. The heater never turns on at the bathroom sink.
FAQ
What breakers does a 27 kW tankless water heater need? At 240 V, 3 two-pole 40 A breakers, one for each 9 kW element drawing 37.5 A. If your inspector applies the 125% continuous-load factor, use 50 A breakers, as long as the label allows that size.
Is 8 AWG wire enough? Yes, on 40 A breakers. 8 AWG copper is rated 40 A as NM-B and 50 A as THHN at 75 °C. At 40 ft the drop is 0.96%. On 50 A breakers, use 8 AWG THHN or 6 AWG NM-B.
Can I run it on a 200 A service? Often, but not automatically. The heater alone adds 112.5 A, about 56% of the service. A load calculation under NEC Article 220 decides it.
How many showers can it run at once in winter? One. With 40 °F water it makes 2.8 GPM at 105 °F. Two 2.0 GPM showers would need 38.1 kW.
How much does a 10-minute shower cost? At 2.0 GPM and a 65 °F rise, a 10-minute shower uses about 3.17 kWh. At an example rate of $0.18 per kWh, that is about $0.57. Use the rate on your own bill.
Case summary
| Item | Result |
|---|---|
| Heater | 27 kW, 240 V, 3 elements of 9 kW |
| Total current | 112.5 A |
| Circuits | 3 × 37.5 A |
| Breakers | 3 × 40 A two-pole (50 A with 125%) |
| Wire per circuit | 8 AWG copper (8 AWG THHN with 125%) |
| Ground per circuit | 10 AWG copper |
| Voltage drop at 40 ft | 0.96% |
| Winter flow at 105 °F | 2.83 GPM |
Different heater size, incoming water temperature or flow? Try the water heater size calculator with your own numbers, and have a licensed electrician pull the permit for the circuits.
Related guide: 27 kW Tankless Water Heater: Breakers and Wire Size
Try it with your own numbersWater Heater Size Calculator (Tank Gallons or Tankless GPM)→Sources and references
- NFPA 70, National Electrical Code (NEC) 110.3(B) (follow listing and instructions), 422.13 (storage-type water heaters as continuous loads), Table 310.16 (ampacity), 334.80 (NM cable at 60 °C), Table 250.122 (grounding conductor), Article 220 (load calculation)
- U.S. Department of Energy – Energy Saver: Sizing a New Water Heater method for sizing tankless heaters from flow rate and temperature rise
- U.S. EPA WaterSense – Showerheads 2.0 GPM WaterSense limit and the 2.5 GPM federal maximum used for shower flows
- U.S. Energy Information Administration – Electricity Monthly Update reference for residential electricity prices; the article uses an example rate and tells readers to use their own bill
- SizeBench water heater size calculator the same flow and power math as this guide, with your own numbers
Standards and data behind our calculators
How we made this guide
Every number in this guide is calculated by the same code as our calculators, from the standards listed above, and the page is tested before publication. Redação Grupo TAAP wrote it; we use automation and AI tools to help draft, never to produce the figures. Thiago André Azevedo Pires, managing editor, reviewed and approved it before publication. Methodology and sources →
Revision history
- · Published
- · Reviewed