Worked case · Electrical

Generator for Furnace, Fridge and Sump Pump: What Size?

An ice storm, a dark house and a basement that floods without its sump pump. Here is the full calculation for a portable generator that keeps the heat on, the food cold and the basement dry, and the safe way to connect it to the panel.

Small wooden house with a roof covered in heavy snow
When a winter storm takes the power out, the furnace blower, the fridge and the sump pump are what the generator has to carry. Photo: Daniela Altorfer / Unsplash

The case: a winter ice storm knocks out power to a house with a gas furnace, a refrigerator, a chest freezer and a 1/2 hp sump pump in the basement. The owner wants to keep the heat on, the food cold and the basement dry, plus lights, the internet and a TV, from a portable generator connected through a 30 A inlet and an interlock on the main panel. The generator sits 25 ft from the house.

Short answer: these loads add up to 2,200 W running and 3,400 W at the moment the largest motor starts. Keeping the continuous load at or below 80% of the generator's rating, you need a generator rated at least 3,000 W running and 3,500 W starting, fed through a 30 A inlet with 10 AWG cord. At 25 ft the cord drops only 0.95%.

Main panel + inlet30 A 2-pole, interlocked10 AWG cord25 ftEssential loads2,200 W120/240 VVoltage drop 0.95%
Figure 1. The setup in this case: a 120/240 V portable generator, 25 ft of 10 AWG cord to a 30 A inlet, and an interlocked breaker feeding the main panel.

1. List the loads you actually need

The first job is a short list, not a wish list. In a winter outage the essentials are the things that protect the house and the people in it: heat, food storage, water removal, light and communication. For each one, write down two numbers: running watts (what it draws once it is going) and starting watts (the brief surge when a motor or compressor kicks on).

The figures below are the ones for this house, taken from the appliance labels and checked with a plug-in energy meter. Yours will differ, so treat the table as a worksheet, not a rule.

Load Running watts Starting watts
Gas furnace (blower, inducer, controls) 600 1,200
Refrigerator 200 1,200
Chest freezer 100 800
Sump pump, 1/2 hp 1,000 2,200
LED lights 150 150
Router, modem, phone chargers 50 50
TV 100 100
Total running 2,200
Sump pump2,200 WFurnace1,200 WRefrigerator1,200 WChest freezer800 WLights150 W
Figure 2. Starting watts of each load in this house. The motors set the surge, and the sump pump is the largest at 2,200 W.

2. Add the largest starting surge, once

You do not add up every starting figure. Motors rarely start at exactly the same instant, so the usual method is:

Peak = total running watts + (starting − running) of the single largest motor

The sump pump has the biggest jump: 2,200 − 1,000 = 1,200 W. So the peak is 2,200 + 1,200 = 3,400 W.

That is the number the generator's starting (or "peak", "surge") rating must cover.

If the sump pump and the refrigerator do happen to start together, the demand briefly reaches 4,400 W. A generator a little short of that will usually bog down for a second and recover, but repeated overloads trip its breaker. The section on common mistakes explains how to avoid the coincidence.

3. Leave headroom on the running rating

A portable generator's running rating is what it can deliver continuously, but running an engine at full output for days shortens its life, burns more fuel per kWh and leaves nothing for the surge. A common rule among installers is to keep the steady load at or below 80% of the running rating:

2,200 W ÷ 0.80 = 2,750 W

Rounded up to the next 500 W, that gives a generator rated 3,000 W running and at least 3,500 W starting. Before you buy, check the outlets: feeding a panel inlet needs a 120/240 V twist-lock outlet, and many smaller models are 120 V only. That outlet is a harder requirement than a few hundred watts either way, and it may push you up a size.

4. Three scenarios side by side

The essentials are rarely the whole story. Someone will want to heat soup in the microwave, and someone will ask about a space heater. Here is how each addition moves the size:

Scenario Running watts Peak watts Generator (running / starting)
A. Essentials only 2,200 3,400 3,000 / 3,500 W
B. A + microwave (1,000 W) 3,200 4,400 4,000 / 4,500 W
C. B + space heater (1,500 W) 4,700 5,900 6,000 / 6,000 W
A. Essentials3,000 WB. + microwave4,000 WC. + space heater6,000 W
Figure 3. Generator running rating needed for each scenario, keeping the steady load at 80% of the rating.

The space heater is the expensive line. A single 1,500 W heater costs more generator than the furnace, fridge and freezer together. If the furnace runs, you do not need it. If the furnace cannot run, a heater warms one room at best.

The practical answer for scenario B is load management, not a bigger machine: run the microwave while the sump pump is quiet, and the 3,000 W generator copes.

5. Connect it the safe way: inlet, cord and interlock

A generator that runs the furnace has to reach the furnace circuit, and furnaces are normally hardwired. That means feeding the panel, and the NEC (Article 702, optional standby systems) requires transfer equipment that makes it impossible for the generator and the utility to be connected at the same time. In a house, that is either a manual transfer switch or a listed interlock kit on the main panel, fed from an outdoor power inlet.

A 30 A, 120/240 V inlet carries up to 30 A × 240 V = 7,200 W, more than any scenario in the table. It pairs with a 30 A two-pole breaker in the panel and a 10 AWG, four-conductor generator cord.

Electrical panel being wired, with rows of breakers and conductors
Figure 4. The generator reaches the furnace through the panel, so the inlet, the interlock and the backfeed breaker have to be matched and listed for that panel. Photo: Troy Bridges / Unsplash

How long can the cord be?

The cord is a branch of the circuit like any other, and voltage drop grows with length. All the loads in this case are 120 V, and in the worst case they all sit on one leg, so the cord carries 18.3 A on one hot and the neutral. With 10 AWG copper (about 1.24 Ω per 1,000 ft, NEC Chapter 9, Table 8):

Cord length Drop with 10 AWG Smallest size for 3% at this load
25 ft 0.95% 12 AWG
50 ft 1.89% 12 AWG
100 ft 3.79% 8 AWG

The right-hand column is what voltage drop alone would ask for. The cord can never be smaller than 10 AWG on a 30 A inlet, whatever the table says, because the cord must match the 30 A rating of the plug, the inlet and the breaker.

02468100255075100125150Cord length (ft)Drop (%)25 ft12 AWG10 AWG8 AWG3% target
Figure 5. Voltage drop at 18.3 A on a 120 V leg by cord size and length. 12 AWG is shown only for comparison: it is too small for a 30 A inlet.

With 10 AWG the 3% line is reached at about 79 ft. Balancing the loads across both legs of the panel roughly halves the current on each hot, which buys margin. During a motor start the current briefly rises to 28.3 A and the drop on 25 ft of cord to 1.46%, which is harmless for a second or two.

Keep the generator outdoors, well away from the house. The CPSC advises at least 20 ft from the home, with the exhaust pointed away from windows, doors and vents. The 25 ft cord in this case allows exactly that.

6. How to read the labels

  • Furnace: the rating plate inside the burner door lists volts and either total amps or a maximum overcurrent device. Watts ≈ volts × amps gives an upper bound; the blower usually accounts for most of it.
  • Refrigerator: the label shows rated amps, which includes the defrost heater. A fridge labeled 6.5 A at 120 V reads as 780 W, but the compressor alone usually draws far less. Measure it with a plug-in meter.
  • Sump and well pumps: look for horsepower, full-load amps and, on some motors, LRA (locked-rotor amps). Volts × LRA is a worst-case starting figure.
  • Generator: the spec sheet gives running and starting watts, the outlets, and runtime at 25% and 50% load. Use the runtime figure that matches your average load.

7. How much energy per day?

Starting watts size the generator; energy decides the fuel. With the furnace blower running about half the time in cold weather, the fridge and freezer cycling about a third of the time and the sump pump about a tenth, this house uses about 14.6 kWh per day, an average of 609 W.

That is barely a fifth of the 3,000 W generator's rating for most of the day. Compare that figure with the runtime-at-25%-load line on the spec sheet to estimate how much fuel to store, and keep it in approved containers outside the living space.

8. Installation and inspection checklist

  • [ ] Permit pulled for the inlet and interlock (most jurisdictions require one)
  • [ ] Interlock kit listed for the exact panel model
  • [ ] 30 A inlet, 30 A two-pole backfeed breaker and 10 AWG cord, all matched
  • [ ] Generator has a 120/240 V outlet that matches the inlet
  • [ ] Neutral-to-ground bonding handled as the generator and transfer equipment manuals require
  • [ ] Generator location at least 20 ft from the house, exhaust away from openings
  • [ ] Battery-powered or battery-backup CO alarms on every level
  • [ ] Furnace, fridge, freezer and sump pump circuits labeled so you know what to switch on

9. Signs of a problem

  • Lights dip hard and the generator labors every time the sump pump starts: you are at the edge of the starting rating.
  • The furnace tries to light, then locks out: some control boards reject a ragged waveform or a floating neutral. Inverter generators and correct bonding usually fix it.
  • The cord or plug feels warm: check the plug for damage and the cord gauge.
  • The generator breaker trips after a few minutes: steady overload. Shed a load and recheck your list.

Common mistakes

  • Sizing on running watts only. A generator rated exactly 2,200 W stalls the first time the sump pump starts.
  • Backfeeding through a dryer outlet with a double-male cord. It can energize the utility line and injure line workers, and it bypasses every safety device. Use an inlet and an interlock or transfer switch.
  • Running the generator in the garage, even with the door open. Carbon monoxide builds up fast and enters the house.
  • Two motors starting together after power returns to the panel. Switch circuits on one at a time, largest motor first, with the generator already running.
  • Using a light-duty extension cord. A 16 AWG cord sized for a lamp overheats at furnace-and-fridge currents.

FAQ

Will a 2,000 W inverter generator run my furnace and fridge? For those two alone, usually yes: in this case they need 800 W running and 1,800 W at the larger start. Add the sump pump and it is no longer enough.

Is a 30 A inlet big enough? For this house, yes. It carries 7,200 W at 240 V, more than scenario C needs (4,700 W running).

How long can my 10 AWG generator cord be? At the 18.3 A worst-case load on one leg, about 79 ft before the drop passes 3%. At 25 ft it is 0.95%.

How much electricity will I use per day? About 14.6 kWh with the duty cycles above, an average of 609 W.

Can I add the microwave? Yes, with a little discipline. The steady load rises to 3,200 W; on the 3,000 W generator, avoid running it while the sump pump is cycling, or step up to 4,000 W.

Case summary

Item Result
Total running load 2,200 W
Peak (largest motor starting) 3,400 W
Generator size 3,000 W running / 3,500 W starting
Connection 30 A inlet + interlock, 30 A 2-pole breaker
Cord 10 AWG, 25 ft, drop 0.95%
Energy per day about 14.6 kWh

List your own loads in the SizeBench generator size calculator to get the running and starting figures for your house before the next storm.

Read also: What Size Whole-House Generator Do I Need?

Try it with your own numbersGenerator Size Calculator→

Sources and references

  1. NFPA 70, National Electrical Code (NEC) Article 702 (transfer equipment for optional standby systems), Article 445 (generators), Chapter 9 Table 8 (conductor resistance used for the cord voltage drop)
  2. U.S. Consumer Product Safety Commission – CO fatalities report and generator safety outdoor-only operation, distance from the house, exhaust away from openings, CO alarms
  3. Ready.gov (FEMA) – Power Outages generator safety and outage preparation used in the checklist
  4. FEMA – Be Prepared for a Power Outage (hazard info sheet) never connect a generator directly to home wiring without proper transfer equipment; fuel storage
  5. SizeBench generator size calculator the same running + largest-surge method, with your own loads

Standards and data behind our calculators

How we made this guide

Every number in this guide is calculated by the same code as our calculators, from the standards listed above, and the page is tested before publication. Redação Grupo TAAP wrote it; we use automation and AI tools to help draft, never to produce the figures. Thiago André Azevedo Pires, managing editor, reviewed and approved it before publication. Methodology and sources →

Revision history

  • · Published
  • · Reviewed