Breaker Size Calculator

Enter the load in amps or watts to get the minimum standard breaker size and a matching wire gauge.

Free, no sign-upInstant resultsUpdated October 2026
Load entered as
A
W
Phase
Breaker size
–
How we calculated this

    For estimating and educational purposes only. Results are approximate and are not a substitute for a licensed professional, the manufacturer's instructions or your local code. Disclaimer

    Embed this calculator on your site

    Free for any website or blog. Copy the code below and paste it into an HTML block. Keep the credit link.

    Electrical cabinet with circuit breakers being adjusted
    Electrical cabinet with circuit breakers being adjustedPhoto: Aleksandr Lyaptsev / Unsplash

    How to size a breaker

    Find the load current, multiply by 125% if the load runs continuously for three hours or more, then round up to the next standard breaker size. The wire must be rated for at least the breaker size so the breaker protects it.

    Continuous load: Breaker ≥ Load amps × 1.25 Non-continuous load: Breaker ≥ Load amps Amps from watts: I = W ÷ V (1φ) · I = W ÷ (1.732 × V) (3φ)

    Example: 32 A Level 2 EV charger

    EV charging is continuous, so 32 × 1.25 = 40 A. The next standard size is a 40 A breaker with 8 AWG copper. 8 AWG works as THHN in conduit (50 A at 75°C) and as NM-B cable (40 A at the 60°C rating).

    Standard breaker sizes (NEC 240.6)

    15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400 A and up.

    Common circuits

    ApplianceTypical breakerCopper wire
    Lighting, bedroom outlets15 A14 AWG
    Kitchen, bathroom, garage outlets20 A12 AWG
    Electric water heater (4,500 W)30 A10 AWG
    Electric dryer30 A10 AWG
    Electric range40–50 A8–6 AWG
    EV charger (48 A)60 A6 AWG

    Breaker size to wire size chart (NEC)

    Standard breaker ratings (NEC 240.6) with the smallest copper and aluminum wire that the breaker can protect, and the largest continuous load allowed on each.

    Show full table
    BreakerMax. continuous load (80%)At 120 VAt 240 VCopper 60 °C (NM-B)Copper 75 °C (THHN)Aluminum 75 °C
    15 A12 A1,440 W2,880 W14 AWG14 AWG12 AWG
    20 A16 A1,920 W3,840 W12 AWG12 AWG10 AWG
    25 A20 A2,400 W4,800 W10 AWG10 AWG10 AWG
    30 A24 A2,880 W5,760 W10 AWG10 AWG8 AWG
    35 A28 A3,360 W6,720 W8 AWG8 AWG8 AWG
    40 A32 A3,840 W7,680 W8 AWG8 AWG8 AWG
    45 A36 A4,320 W8,640 W6 AWG8 AWG6 AWG
    50 A40 A4,800 W9,600 W6 AWG8 AWG6 AWG
    60 A48 A5,760 W11,520 W4 AWG6 AWG4 AWG
    70 A56 A6,720 W13,440 W4 AWG4 AWG3 AWG
    80 A64 A7,680 W15,360 W3 AWG4 AWG2 AWG
    90 A72 A8,640 W17,280 W2 AWG3 AWG2 AWG
    100 A80 A9,600 W19,200 W1 AWG3 AWG1 AWG
    110 A88 A10,560 W21,120 W–2 AWG1/0 AWG
    125 A100 A12,000 W24,000 W–1 AWG2/0 AWG
    150 A120 A14,400 W28,800 W–1/0 AWG3/0 AWG
    175 A140 A16,800 W33,600 W–2/0 AWG4/0 AWG
    200 A160 A19,200 W38,400 W–3/0 AWG250 kcmil
    225 A180 A21,600 W43,200 W–4/0 AWG300 kcmil
    250 A200 A24,000 W48,000 W–250 kcmil350 kcmil
    300 A240 A28,800 W57,600 W–350 kcmil500 kcmil
    350 A280 A33,600 W67,200 W–500 kcmilparallel runs
    400 A320 A38,400 W76,800 W–parallel runsparallel runs

    Wire from NEC Table 310.16 with the 240.4(D) small-conductor limits (14 AWG = 15 A, 12 AWG = 20 A, 10 AWG = 30 A copper). 60 °C applies to NM-B cable and to most equipment terminals up to 100 A (110.14(C)); “–” in that column = 75 °C terminals required. Continuous loads (3 h or more) may use 80% of the breaker rating. No temperature or bundling derating, short runs; check voltage drop for long runs. Above 500 kcmil, conductors run in parallel.

    Frequently asked questions

    What is the 80% rule for breakers?

    A standard breaker should carry no more than 80% of its rating continuously. It is the same as sizing the breaker at 125% of the continuous load.

    What size breaker for a 5,000 watt heater at 240 V?

    5000 ÷ 240 = 20.8 A; × 125% = 26 A, so a 30 A breaker with 10 AWG copper.

    Can I put a bigger breaker on the same wire?

    No. The breaker protects the wire. Upsizing the breaker without upsizing the wire is a fire hazard and a code violation.