How to size a breaker
Find the load current, multiply by 125% if the load runs continuously for three hours or more, then round up to the next standard breaker size. The wire must be rated for at least the breaker size so the breaker protects it.
Example: 32 A Level 2 EV charger
EV charging is continuous, so 32 × 1.25 = 40 A. The next standard size is a 40 A breaker with 8 AWG copper. 8 AWG works as THHN in conduit (50 A at 75°C) and as NM-B cable (40 A at the 60°C rating).
Standard breaker sizes (NEC 240.6)
15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400 A and up.
Common circuits
| Appliance | Typical breaker | Copper wire |
|---|---|---|
| Lighting, bedroom outlets | 15 A | 14 AWG |
| Kitchen, bathroom, garage outlets | 20 A | 12 AWG |
| Electric water heater (4,500 W) | 30 A | 10 AWG |
| Electric dryer | 30 A | 10 AWG |
| Electric range | 40–50 A | 8–6 AWG |
| EV charger (48 A) | 60 A | 6 AWG |
Breaker size to wire size chart (NEC)
Standard breaker ratings (NEC 240.6) with the smallest copper and aluminum wire that the breaker can protect, and the largest continuous load allowed on each.
Show full table
| Breaker | Max. continuous load (80%) | At 120 V | At 240 V | Copper 60 °C (NM-B) | Copper 75 °C (THHN) | Aluminum 75 °C |
|---|---|---|---|---|---|---|
| 15 A | 12 A | 1,440 W | 2,880 W | 14 AWG | 14 AWG | 12 AWG |
| 20 A | 16 A | 1,920 W | 3,840 W | 12 AWG | 12 AWG | 10 AWG |
| 25 A | 20 A | 2,400 W | 4,800 W | 10 AWG | 10 AWG | 10 AWG |
| 30 A | 24 A | 2,880 W | 5,760 W | 10 AWG | 10 AWG | 8 AWG |
| 35 A | 28 A | 3,360 W | 6,720 W | 8 AWG | 8 AWG | 8 AWG |
| 40 A | 32 A | 3,840 W | 7,680 W | 8 AWG | 8 AWG | 8 AWG |
| 45 A | 36 A | 4,320 W | 8,640 W | 6 AWG | 8 AWG | 6 AWG |
| 50 A | 40 A | 4,800 W | 9,600 W | 6 AWG | 8 AWG | 6 AWG |
| 60 A | 48 A | 5,760 W | 11,520 W | 4 AWG | 6 AWG | 4 AWG |
| 70 A | 56 A | 6,720 W | 13,440 W | 4 AWG | 4 AWG | 3 AWG |
| 80 A | 64 A | 7,680 W | 15,360 W | 3 AWG | 4 AWG | 2 AWG |
| 90 A | 72 A | 8,640 W | 17,280 W | 2 AWG | 3 AWG | 2 AWG |
| 100 A | 80 A | 9,600 W | 19,200 W | 1 AWG | 3 AWG | 1 AWG |
| 110 A | 88 A | 10,560 W | 21,120 W | – | 2 AWG | 1/0 AWG |
| 125 A | 100 A | 12,000 W | 24,000 W | – | 1 AWG | 2/0 AWG |
| 150 A | 120 A | 14,400 W | 28,800 W | – | 1/0 AWG | 3/0 AWG |
| 175 A | 140 A | 16,800 W | 33,600 W | – | 2/0 AWG | 4/0 AWG |
| 200 A | 160 A | 19,200 W | 38,400 W | – | 3/0 AWG | 250 kcmil |
| 225 A | 180 A | 21,600 W | 43,200 W | – | 4/0 AWG | 300 kcmil |
| 250 A | 200 A | 24,000 W | 48,000 W | – | 250 kcmil | 350 kcmil |
| 300 A | 240 A | 28,800 W | 57,600 W | – | 350 kcmil | 500 kcmil |
| 350 A | 280 A | 33,600 W | 67,200 W | – | 500 kcmil | parallel runs |
| 400 A | 320 A | 38,400 W | 76,800 W | – | parallel runs | parallel runs |
Wire from NEC Table 310.16 with the 240.4(D) small-conductor limits (14 AWG = 15 A, 12 AWG = 20 A, 10 AWG = 30 A copper). 60 °C applies to NM-B cable and to most equipment terminals up to 100 A (110.14(C)); “–” in that column = 75 °C terminals required. Continuous loads (3 h or more) may use 80% of the breaker rating. No temperature or bundling derating, short runs; check voltage drop for long runs. Above 500 kcmil, conductors run in parallel.
Frequently asked questions
What is the 80% rule for breakers?
A standard breaker should carry no more than 80% of its rating continuously. It is the same as sizing the breaker at 125% of the continuous load.
What size breaker for a 5,000 watt heater at 240 V?
5000 ÷ 240 = 20.8 A; × 125% = 26 A, so a 30 A breaker with 10 AWG copper.
Can I put a bigger breaker on the same wire?
No. The breaker protects the wire. Upsizing the breaker without upsizing the wire is a fire hazard and a code violation.