Wire size for 15 amps by distance (120 V, 3% drop)
| One-way distance | Copper | Drop | Aluminum |
|---|---|---|---|
| 25 ft | 14 AWG | 1.92% | 12 AWG |
| 50 ft | 12 AWG | 2.41% | 10 AWG |
| 75 ft | 10 AWG | 2.27% | 8 AWG |
| 100 ft | 8 AWG | 1.91% | 6 AWG |
| 150 ft | 8 AWG | 2.87% | 4 AWG |
| 200 ft | 6 AWG | 2.46% | 4 AWG |
| 250 ft | 4 AWG | 1.93% | 3 AWG |
| 300 ft | 4 AWG | 2.31% | 2 AWG |
Single-phase 120 V, 75°C terminals, non-continuous load. For continuous loads (3+ hours) size for 19 A.
Common 15 A circuits
15 amp circuits typically feed lighting and bedroom outlets. The breaker protects the wire, so never pair a 15 A breaker with wire rated below 15 A.
Frequently asked questions
Can I use 14 AWG wire on a 15 amp breaker?
Yes. 14 AWG copper is rated at least 15 A even in the 60°C column, so it works for NM-B cable and THHN alike, as long as voltage drop is acceptable.
How far can I run 14 AWG wire at 15 amps?
At 120 V with a 3% voltage-drop limit, about 25 ft one way. Beyond that, go up one size.