What Size Wire for 15 Amps?

Answer
14 AWG copper (THHN, 75°C)

For a 15 A circuit, the smallest copper wire is 14 AWG in conduit (75°C rating) or 14 AWG if you use NM-B (Romex) cable, which is limited to the 60°C column. Aluminum needs 12 AWG. That holds up to about 25 ft at 120 V before voltage drop passes 3%.

Free, no sign-upInstant resultsUpdated October 2026
A
%
3% branch, 5% total (NEC note)
Phase
Conductor
Recommended wire
–
How we calculated this

    For estimating and educational purposes only. Results are approximate and are not a substitute for a licensed professional, the manufacturer's instructions or your local code. Disclaimer

    Wire size for 15 amps by distance (120 V, 3% drop)

    One-way distanceCopperDropAluminum
    25 ft14 AWG1.92%12 AWG
    50 ft12 AWG2.41%10 AWG
    75 ft10 AWG2.27%8 AWG
    100 ft8 AWG1.91%6 AWG
    150 ft8 AWG2.87%4 AWG
    200 ft6 AWG2.46%4 AWG
    250 ft4 AWG1.93%3 AWG
    300 ft4 AWG2.31%2 AWG

    Single-phase 120 V, 75°C terminals, non-continuous load. For continuous loads (3+ hours) size for 19 A.

    Common 15 A circuits

    15 amp circuits typically feed lighting and bedroom outlets. The breaker protects the wire, so never pair a 15 A breaker with wire rated below 15 A.

    Frequently asked questions

    Can I use 14 AWG wire on a 15 amp breaker?

    Yes. 14 AWG copper is rated at least 15 A even in the 60°C column, so it works for NM-B cable and THHN alike, as long as voltage drop is acceptable.

    How far can I run 14 AWG wire at 15 amps?

    At 120 V with a 3% voltage-drop limit, about 25 ft one way. Beyond that, go up one size.

    Open the full calculator: Wire Size Calculator →