What Size Wire for 200 Amps?

Answer
3/0 AWG copper (THHN, 75°C)

For a 200 A circuit, the smallest copper wire is 3/0 AWG in conduit (75°C rating) or 250 kcmil if you use NM-B (Romex) cable, which is limited to the 60°C column. Aluminum needs 250 kcmil. That holds up to about 200 ft at 240 V before voltage drop passes 3%.

Free, no sign-upInstant resultsUpdated October 2026
A
%
3% branch, 5% total (NEC note)
Phase
Conductor
Recommended wire
–
How we calculated this

    For estimating and educational purposes only. Results are approximate and are not a substitute for a licensed professional, the manufacturer's instructions or your local code. Disclaimer

    Wire size for 200 amps by distance (240 V, 3% drop)

    One-way distanceCopperDropAluminum
    25 ft3/0 AWG0.32%250 kcmil
    50 ft3/0 AWG0.64%250 kcmil
    75 ft3/0 AWG0.96%250 kcmil
    100 ft3/0 AWG1.28%250 kcmil
    150 ft3/0 AWG1.92%250 kcmil
    200 ft3/0 AWG2.55%250 kcmil
    250 ft4/0 AWG2.53%300 kcmil
    300 ft250 kcmil2.57%400 kcmil

    Single-phase 240 V, 75°C terminals, non-continuous load. For continuous loads (3+ hours) size for 250 A.

    Common 200 A circuits

    200 amp circuits typically feed 200 A residential services. The breaker protects the wire, so never pair a 200 A breaker with wire rated below 200 A.

    Service entrance conductors

    For a 200 A dwelling service (not a subpanel feeder), NEC 310.12 lets the conductors be sized at 83% of the rating, so 2/0 AWG copper or 4/0 AWG aluminum is typical. Feeders to a subpanel use the full 200 A table above.

    Frequently asked questions

    Can I use 250 kcmil wire on a 200 amp breaker?

    Yes. 250 kcmil copper is rated at least 200 A even in the 60°C column, so it works for NM-B cable and THHN alike, as long as voltage drop is acceptable.

    How far can I run 3/0 AWG wire at 200 amps?

    At 240 V with a 3% voltage-drop limit, about 200 ft one way. Beyond that, go up one size.