For a 30 A circuit, the smallest copper wire is 10 AWG in conduit (75°C rating) or 10 AWG if you use NM-B (Romex) cable, which is limited to the 60°C column. Aluminum needs 8 AWG. That holds up to about 75 ft at 240 V before voltage drop passes 3%.
Free, no sign-upInstant resultsUpdated October 2026
Recommended wire
–
How we calculated this
Was this calculator helpful?Thanks for the feedback!
For estimating and educational purposes only. Results are approximate and are not a substitute for a licensed professional, the manufacturer's instructions or your local code. Disclaimer
Wire size for 30 amps by distance (240 V, 3% drop)
One-way distance
Copper
Drop
Aluminum
25 ft
10 AWG
0.76%
8 AWG
50 ft
10 AWG
1.51%
8 AWG
75 ft
10 AWG
2.27%
8 AWG
100 ft
8 AWG
1.91%
6 AWG
150 ft
8 AWG
2.87%
4 AWG
200 ft
6 AWG
2.46%
4 AWG
250 ft
4 AWG
1.93%
3 AWG
300 ft
4 AWG
2.31%
2 AWG
Single-phase 240 V, 75°C terminals, non-continuous load. For continuous loads (3+ hours) size for 38 A.
Common 30 A circuits
30 amp circuits typically feed water heaters, dryers and small A/C units. The breaker protects the wire, so never pair a 30 A breaker with wire rated below 30 A.