How to read the chart
Find the load current, then pick the first size whose ampacity is equal to or greater than the breaker rating. For continuous loads (3 hours or more, like EV chargers and water heaters) size the breaker and wire for 125% of the load.
Why aluminum is one or two sizes larger
Aluminum conducts about 61% as well as copper, so the same ampacity needs a larger cross-section. That is why a 100 A feeder is 3 AWG copper but 1 AWG aluminum.
Frequently asked questions
What size wire for 20 amps?
12 AWG copper. 14 AWG is limited to 15 A.
What size wire for 30 amps?
10 AWG copper, or 8 AWG aluminum.
What size wire for 50 amps?
6 AWG copper NM-B or 8 AWG copper THHN in conduit (75 °C terminals), or 6 AWG aluminum.
What size wire for 100 amps?
3 AWG copper or 1 AWG aluminum at 75 °C. Dwelling services may use NEC 310.12: 4 AWG copper or 2 AWG aluminum.