Wire Size Chart: AWG Ampacity for Copper and Aluminum
Answer
14 AWG = 15 A · 12 AWG = 20 A · 10 AWG = 30 A
Use the 75 °C column for THHN/THWN in conduit and most breaker terminals, and the 60 °C column for NM-B (Romex) house cable. Small conductors are capped at 15, 20 and 30 A by NEC 240.4(D).
Free, no sign-upInstant resultsUpdated October 2026
AWG ampacity chart (NEC 310.16, 30 °C ambient)
Wire size
mm²
Copper 60 °C (NM-B)
Copper 75 °C (THHN)
Aluminum 75 °C
14 AWG
2.08
15 A
15 A
–
12 AWG
3.31
20 A
20 A
15 A
10 AWG
5.26
30 A
30 A
25 A
8 AWG
8.37
40 A
50 A
40 A
6 AWG
13.3
55 A
65 A
50 A
4 AWG
21.2
70 A
85 A
65 A
3 AWG
26.7
85 A
100 A
75 A
2 AWG
33.6
95 A
115 A
90 A
1 AWG
42.4
110 A
130 A
100 A
1/0 AWG
53.5
–
150 A
120 A
2/0 AWG
67.4
–
175 A
135 A
3/0 AWG
85.0
–
200 A
155 A
4/0 AWG
107.0
–
230 A
180 A
250 kcmil
127.0
–
255 A
205 A
300 kcmil
152.0
–
285 A
230 A
350 kcmil
177.0
–
310 A
250 A
400 kcmil
203.0
–
335 A
270 A
500 kcmil
253.0
–
380 A
310 A
No more than three current-carrying conductors in a raceway or cable. For more conductors or hot locations, apply NEC adjustment factors. Long runs need a larger size for voltage drop: use the calculator below.
Recommended wire
–
How we calculated this
Was this calculator helpful?Thanks for the feedback!
For estimating and educational purposes only. Results are approximate and are not a substitute for a licensed professional, the manufacturer's instructions or your local code. Disclaimer
Find the load current, then pick the first size whose ampacity is equal to or greater than the breaker rating. For continuous loads (3 hours or more, like EV chargers and water heaters) size the breaker and wire for 125% of the load.
Why aluminum is one or two sizes larger
Aluminum conducts about 61% as well as copper, so the same ampacity needs a larger cross-section. That is why a 100 A feeder is 3 AWG copper but 1 AWG aluminum.