For a 20 A circuit, the smallest copper wire is 12 AWG in conduit (75°C rating) or 12 AWG if you use NM-B (Romex) cable, which is limited to the 60°C column. Aluminum needs 10 AWG. That holds up to about 25 ft at 120 V before voltage drop passes 3%.
Free, no sign-upInstant resultsUpdated October 2026
Recommended wire
–
How we calculated this
Was this calculator helpful?Thanks for the feedback!
For estimating and educational purposes only. Results are approximate and are not a substitute for a licensed professional, the manufacturer's instructions or your local code. Disclaimer
Wire size for 20 amps by distance (120 V, 3% drop)
One-way distance
Copper
Drop
Aluminum
25 ft
12 AWG
1.61%
10 AWG
50 ft
10 AWG
2.02%
8 AWG
75 ft
8 AWG
1.91%
6 AWG
100 ft
8 AWG
2.55%
6 AWG
150 ft
6 AWG
2.46%
4 AWG
200 ft
4 AWG
2.05%
3 AWG
250 ft
4 AWG
2.57%
2 AWG
300 ft
3 AWG
2.45%
1 AWG
Single-phase 120 V, 75°C terminals, non-continuous load. For continuous loads (3+ hours) size for 25 A.
Common 20 A circuits
20 amp circuits typically feed kitchen, bathroom and garage outlets. The breaker protects the wire, so never pair a 20 A breaker with wire rated below 20 A.