What Size Wire for 100 Amps?

Answer
3 AWG copper (THHN, 75°C)

For a 100 A circuit, the smallest copper wire is 3 AWG in conduit (75°C rating) or 1 AWG if you use NM-B (Romex) cable, which is limited to the 60°C column. Aluminum needs 1 AWG. That holds up to about 100 ft at 240 V before voltage drop passes 3%.

Free, no sign-upInstant resultsUpdated October 2026
A
%
3% branch, 5% total (NEC note)
Phase
Conductor
Recommended wire
–
How we calculated this

    For estimating and educational purposes only. Results are approximate and are not a substitute for a licensed professional, the manufacturer's instructions or your local code. Disclaimer

    Wire size for 100 amps by distance (240 V, 3% drop)

    One-way distanceCopperDropAluminum
    25 ft3 AWG0.51%1 AWG
    50 ft3 AWG1.02%1 AWG
    75 ft3 AWG1.53%1 AWG
    100 ft3 AWG2.04%1 AWG
    150 ft2 AWG2.43%1/0 AWG
    200 ft1 AWG2.57%2/0 AWG
    250 ft1/0 AWG2.54%3/0 AWG
    300 ft2/0 AWG2.42%4/0 AWG

    Single-phase 240 V, 75°C terminals, non-continuous load. For continuous loads (3+ hours) size for 125 A.

    Common 100 A circuits

    100 amp circuits typically feed subpanels and small services. The breaker protects the wire, so never pair a 100 A breaker with wire rated below 100 A.

    Service entrance conductors

    For a 100 A dwelling service (not a subpanel feeder), NEC 310.12 lets the conductors be sized at 83% of the rating, so 4 AWG copper or 2 AWG aluminum is typical. Feeders to a subpanel use the full 100 A table above.

    Frequently asked questions

    Can I use 1 AWG wire on a 100 amp breaker?

    Yes. 1 AWG copper is rated at least 100 A even in the 60°C column, so it works for NM-B cable and THHN alike, as long as voltage drop is acceptable.

    How far can I run 3 AWG wire at 100 amps?

    At 240 V with a 3% voltage-drop limit, about 100 ft one way. Beyond that, go up one size.

    Open the full calculator: Wire Size Calculator →