Wire size for 60 amps by distance (240 V, 3% drop)
| One-way distance | Copper | Drop | Aluminum |
|---|---|---|---|
| 25 ft | 6 AWG | 0.61% | 4 AWG |
| 50 ft | 6 AWG | 1.23% | 4 AWG |
| 75 ft | 6 AWG | 1.84% | 4 AWG |
| 100 ft | 6 AWG | 2.46% | 4 AWG |
| 150 ft | 4 AWG | 2.31% | 2 AWG |
| 200 ft | 3 AWG | 2.45% | 1 AWG |
| 250 ft | 2 AWG | 2.43% | 1/0 AWG |
| 300 ft | 2 AWG | 2.91% | 2/0 AWG |
Single-phase 240 V, 75°C terminals, non-continuous load. For continuous loads (3+ hours) size for 75 A.
Common 60 A circuits
60 amp circuits typically feed 48 A EV chargers, subpanels and tankless heaters. The breaker protects the wire, so never pair a 60 A breaker with wire rated below 60 A.
Frequently asked questions
Can I use 4 AWG wire on a 60 amp breaker?
Yes. 4 AWG copper is rated at least 60 A even in the 60°C column, so it works for NM-B cable and THHN alike, as long as voltage drop is acceptable.
How far can I run 6 AWG wire at 60 amps?
At 240 V with a 3% voltage-drop limit, about 100 ft one way. Beyond that, go up one size.