What Size Wire for 60 Amps?

Answer
6 AWG copper (THHN, 75°C)

For a 60 A circuit, the smallest copper wire is 6 AWG in conduit (75°C rating) or 4 AWG if you use NM-B (Romex) cable, which is limited to the 60°C column. Aluminum needs 4 AWG. That holds up to about 100 ft at 240 V before voltage drop passes 3%.

Free, no sign-upInstant resultsUpdated October 2026
A
%
3% branch, 5% total (NEC note)
Phase
Conductor
Recommended wire
–
How we calculated this

    For estimating and educational purposes only. Results are approximate and are not a substitute for a licensed professional, the manufacturer's instructions or your local code. Disclaimer

    Wire size for 60 amps by distance (240 V, 3% drop)

    One-way distanceCopperDropAluminum
    25 ft6 AWG0.61%4 AWG
    50 ft6 AWG1.23%4 AWG
    75 ft6 AWG1.84%4 AWG
    100 ft6 AWG2.46%4 AWG
    150 ft4 AWG2.31%2 AWG
    200 ft3 AWG2.45%1 AWG
    250 ft2 AWG2.43%1/0 AWG
    300 ft2 AWG2.91%2/0 AWG

    Single-phase 240 V, 75°C terminals, non-continuous load. For continuous loads (3+ hours) size for 75 A.

    Common 60 A circuits

    60 amp circuits typically feed 48 A EV chargers, subpanels and tankless heaters. The breaker protects the wire, so never pair a 60 A breaker with wire rated below 60 A.

    Frequently asked questions

    Can I use 4 AWG wire on a 60 amp breaker?

    Yes. 4 AWG copper is rated at least 60 A even in the 60°C column, so it works for NM-B cable and THHN alike, as long as voltage drop is acceptable.

    How far can I run 6 AWG wire at 60 amps?

    At 240 V with a 3% voltage-drop limit, about 100 ft one way. Beyond that, go up one size.

    Open the full calculator: Wire Size Calculator →