Voltage drop by wire size (100 A, 50 ft, 240 V)
| Copper wire | Drop (V) | Drop (%) | Within 3% |
|---|---|---|---|
| 3 AWG | 2.45 V | 1.02% | ✓ |
| 2 AWG | 1.94 V | 0.81% | ✓ |
| 1 AWG | 1.54 V | 0.64% | ✓ |
| 1/0 AWG | 1.22 V | 0.51% | ✓ |
| 2/0 AWG | 0.97 V | 0.40% | ✓ |
Voltage drop = 2 × 50 ft × 100 A × resistance ÷ 1000. Keeping it under 3% on branch circuits (5% total) is the NEC recommendation in the informational notes to 210.19 and 215.2.
Frequently asked questions
Is 3 AWG enough for 100 amps at 50 feet?
It carries 100 A, but at 50 ft the voltage drop is 1.0%, which is acceptable.
Does the distance include the return wire?
No. Enter the one-way distance; the formula already counts both conductors.