What Size Wire for 50 Amps?

Answer
8 AWG copper (THHN, 75°C)

For a 50 A circuit, the smallest copper wire is 8 AWG in conduit (75°C rating) or 6 AWG if you use NM-B (Romex) cable, which is limited to the 60°C column. Aluminum needs 6 AWG. That holds up to about 75 ft at 240 V before voltage drop passes 3%.

Free, no sign-upInstant resultsUpdated October 2026
A
%
3% branch, 5% total (NEC note)
Phase
Conductor
Recommended wire
–
How we calculated this

    For estimating and educational purposes only. Results are approximate and are not a substitute for a licensed professional, the manufacturer's instructions or your local code. Disclaimer

    Wire size for 50 amps by distance (240 V, 3% drop)

    One-way distanceCopperDropAluminum
    25 ft8 AWG0.80%6 AWG
    50 ft8 AWG1.59%6 AWG
    75 ft8 AWG2.39%6 AWG
    100 ft6 AWG2.05%4 AWG
    150 ft4 AWG1.93%3 AWG
    200 ft4 AWG2.57%2 AWG
    250 ft3 AWG2.55%1 AWG
    300 ft2 AWG2.43%1/0 AWG

    Single-phase 240 V, 75°C terminals, non-continuous load. For continuous loads (3+ hours) size for 62 A.

    Common 50 A circuits

    50 amp circuits typically feed ranges, EV chargers and hot tubs. The breaker protects the wire, so never pair a 50 A breaker with wire rated below 50 A.

    What Size Wire for 50 Amps?
    Save to Pinterest

    Frequently asked questions

    Can I use 6 AWG wire on a 50 amp breaker?

    Yes. 6 AWG copper is rated at least 50 A even in the 60°C column, so it works for NM-B cable and THHN alike, as long as voltage drop is acceptable.

    How far can I run 8 AWG wire at 50 amps?

    At 240 V with a 3% voltage-drop limit, about 75 ft one way. Beyond that, go up one size.

    Open the full calculator: Wire Size Calculator →