Voltage drop by wire size (30 A, 50 ft, 240 V)
| Copper wire | Drop (V) | Drop (%) | Within 3% |
|---|---|---|---|
| 10 AWG | 3.63 V | 1.51% | ✓ |
| 8 AWG | 2.29 V | 0.95% | ✓ |
| 6 AWG | 1.47 V | 0.61% | ✓ |
| 4 AWG | 0.92 V | 0.39% | ✓ |
| 3 AWG | 0.73 V | 0.31% | ✓ |
Voltage drop = 2 × 50 ft × 30 A × resistance ÷ 1000. Keeping it under 3% on branch circuits (5% total) is the NEC recommendation in the informational notes to 210.19 and 215.2.
Frequently asked questions
Is 10 AWG enough for 30 amps at 50 feet?
It carries 30 A, but at 50 ft the voltage drop is 1.5%, which is acceptable.
Does the distance include the return wire?
No. Enter the one-way distance; the formula already counts both conductors.