What Size Wire for 50 Amps at 50 Feet?

Answer
8 AWG copper

At 50 ft one way on a 240 V circuit, 8 AWG copper keeps voltage drop at 1.59%, under the recommended 3%. Ampacity alone would allow 8 AWG, but voltage drop decides the size at this distance. In aluminum, use 6 AWG.

Free, no sign-upInstant resultsUpdated October 2026
A
%
3% branch, 5% total (NEC note)
Phase
Conductor
Recommended wire
–
How we calculated this

    For estimating and educational purposes only. Results are approximate and are not a substitute for a licensed professional, the manufacturer's instructions or your local code. Disclaimer

    Voltage drop by wire size (50 A, 50 ft, 240 V)

    Copper wireDrop (V)Drop (%)Within 3%
    8 AWG3.82 V1.59%✓
    6 AWG2.46 V1.02%✓
    4 AWG1.54 V0.64%✓
    3 AWG1.23 V0.51%✓
    2 AWG0.97 V0.40%✓

    Voltage drop = 2 × 50 ft × 50 A × resistance ÷ 1000. Keeping it under 3% on branch circuits (5% total) is the NEC recommendation in the informational notes to 210.19 and 215.2.

    Frequently asked questions

    Is 8 AWG enough for 50 amps at 50 feet?

    It carries 50 A, but at 50 ft the voltage drop is 1.6%, which is acceptable.

    Does the distance include the return wire?

    No. Enter the one-way distance; the formula already counts both conductors.

    Open the full calculator: Wire Size Calculator →