Voltage drop by wire size (100 A, 100 ft, 240 V)
| Copper wire | Drop (V) | Drop (%) | Within 3% |
|---|---|---|---|
| 3 AWG | 4.90 V | 2.04% | ✓ |
| 2 AWG | 3.88 V | 1.62% | ✓ |
| 1 AWG | 3.08 V | 1.28% | ✓ |
| 1/0 AWG | 2.44 V | 1.02% | ✓ |
| 2/0 AWG | 1.93 V | 0.81% | ✓ |
Voltage drop = 2 × 100 ft × 100 A × resistance ÷ 1000. Keeping it under 3% on branch circuits (5% total) is the NEC recommendation in the informational notes to 210.19 and 215.2.
Frequently asked questions
Is 3 AWG enough for 100 amps at 100 feet?
It carries 100 A, but at 100 ft the voltage drop is 2.0%, which is acceptable.
Does the distance include the return wire?
No. Enter the one-way distance; the formula already counts both conductors.