Wire size for 150 amps by distance (240 V, 3% drop)
| One-way distance | Copper | Drop | Aluminum |
|---|---|---|---|
| 25 ft | 1/0 AWG | 0.38% | 3/0 AWG |
| 50 ft | 1/0 AWG | 0.76% | 3/0 AWG |
| 75 ft | 1/0 AWG | 1.14% | 3/0 AWG |
| 100 ft | 1/0 AWG | 1.53% | 3/0 AWG |
| 150 ft | 1/0 AWG | 2.29% | 3/0 AWG |
| 200 ft | 2/0 AWG | 2.42% | 4/0 AWG |
| 250 ft | 3/0 AWG | 2.39% | 250 kcmil |
| 300 ft | 3/0 AWG | 2.87% | 300 kcmil |
Single-phase 240 V, 75°C terminals, non-continuous load. For continuous loads (3+ hours) size for 188 A.
Common 150 A circuits
150 amp circuits typically feed feeders and 150 A services. The breaker protects the wire, so never pair a 150 A breaker with wire rated below 150 A.
Service entrance conductors
For a 150 A dwelling service (not a subpanel feeder), NEC 310.12 lets the conductors be sized at 83% of the rating, so 1 AWG copper or 2/0 AWG aluminum is typical. Feeders to a subpanel use the full 150 A table above.
Frequently asked questions
Can I use 3/0 AWG wire on a 150 amp breaker?
Yes. 3/0 AWG copper is rated at least 150 A even in the 60°C column, so it works for NM-B cable and THHN alike, as long as voltage drop is acceptable.
How far can I run 1/0 AWG wire at 150 amps?
At 240 V with a 3% voltage-drop limit, about 150 ft one way. Beyond that, go up one size.